You may also be interested in
Proximity sensor, Control device, Safety switch, Safety device, Intercom
Text version of the page
33
NAS 311 AS
¤ 40
¤ 29
37,8
85
97,8
M 12
M 12
85
• E-STOP station
• Integrated AS-Interface interface
• AS-Interface LED and status display
• AS-Interface M12 connector
• Thermoplastic or metal
actuators and enclosures
• Pull to reset
• Resistant to chemicals
• Protection class IP 65
Ordering details
NAS 311 À-AS Á
No. Option Description
À ST1 Connector
Á Thermoplastic enclosure
M Metal enclosure
MH Metal enclosure and
push button with
protection collar
Technical data
Standards: EN 50295, EN 60947-5-1,
EN ISO 13849-1, IEC 61508
Enclosure: glass-fibre reinforced
polyamide nylon,
self-extinguishing;
metal enclosure,
paint finish
Emergency-Stop button: thermoplastic
or aluminium
AS-Interface
connection type: connector M12 x 1
Protection class: IP 65
AS-Interface
operating voltage: 26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
AS-Interface operating current: £ 50 mA
AS-Interface specification:
(V 2.1) Profile: S-7.B
IO-Code: 0x7
ID-Code: 0xB
ID-Code1: 0xF
ID-Code2: 0xE
AS-I inputs:
contact 1: data bits D0 /D1 = static code 00
or dynamic code transmission
contact 2: data bits D2 /D3 = static code 00
or dynamic code transmission
Parameter bits: P0 … P3 not used
Input module address: default on address 0,
programmable
Indications:
AS-Interface: voltage LED green,
communication LED red
Enabling status: LED yellow
EMC rating: conforming to
EMC Directive
Ambient temperature: – 25 °C … + 60 ºC
Storage and transport
temperature: – 25 °C … + 85 ºC
Classification :
Standards: EN ISO 13849-1; IEC 61508
PL: up to e
Category: up to 4
PFH value: 3,16 x 10-8 /h
for max. 5.000 operations/year
SIL: up to 3
Service life: 20 years
Note
The addressing must take place via the M12
connector.
1: AS-Interface +
2: spare
3: AS-Interface –
4: spare
1 4
2 3
Approvals
F C
R C
S OR
AS-Interface Safety at Work
|
|