30
AST ... ST-AS
• Input module with M12 connector (AS-i)
• 2 safe inputs for mechanical contacts
• Connection of NC/NC contact
or NC/NO contact combination
• Cross-wire monitoring
• Magnetic drive through
AS-Interface output
• Solenoid power supply via an external
24 VDC power supply(max. 0.5 A)
• AS-Interface LED and status display
• AS-Interface M12 connector
• Thermoplastic enclosure
• Long life
• Protection class IP 67
Approvals
F
Ordering details
AST ÀÁ-ASÂÃ
No. Option Description
À 02 1 NC/1 NC
11 1 NO/1 NC
Á AS-i connection:
ST M12 connector
L Cable (2m)
 Sensor connection:
2 2 x 2-single conductors
(2 safety inputs)
4 1 x 4-single conductors
(2 safety inputs)
6 1 x 6-single conductors
(2 safety inputs and
1 semiconductor output)
C
Technical data
Standards: EN 50295, EN 60947-5-1,
EN ISO 13849-1, IEC 61508
Enclosure: glass-fibre reinforced
thermoplastic, self-extinguishing
AS-Interface
connection type: (see ordering data)
Protection class: IP 67
AS-Interface
operating voltage: 26.5 ... 31.6 VDC,
via AS-Interface, reverse-polarity proof
AS-Interface
operating current: £ 50 mA
AS-Interface specification:
(V 2.1) Profile S-7.B
IO-Code 0x7
ID-Code 0xB
ID-Code1 0xF
ID-Code2 0xE
AS-I inputs:
contact 1: data bits D0 /D1 = static code 00
or dynamic code transmission
contact 2: data bits D2 /D3 = static code 00
or dynamic code transmission
Outputs: A0 Solenoid control (AST ...6)
(24 VDC, max. 500 mA)
A1...A3 not used
Parameter bits: P0 … P3 not used
Input module address: default on address 0,
programmable via the
AS-Interface Master or
Hand-held programming device
Indications: AS-Interface:
supply voltage green LED,
communication red LED,
blinking = cross-wire short
Enabling status: LED1/contact1,
yellow/contact2
EMC rating: conforming to
EMC Directive
Ambient temperature: – 25 °C … + 55 ºC
Storage and transport
temperature: – 25 °C … + 85 ºC
Classification:
Standards: EN ISO 13849-1; IEC 61508
PL: up to e
Category: up to 4
PFH value: 2,04 x 10-9 /h
SIL: up to 3
Service life: 20 years
AST ... L-AS
• Input module with cable (AS-i), length 2 m
2
70 ca. 2000
66
¤28
25
M30x1,5
16,5
2
70 ca. 2000
66
¤28
25
M30x1,5
ca. 2000
Ordering details
No. Option Description
à Sensor connection:
ST M12 connector with 2m
cable (2 x 2-single conductors
or 1 x 4-single
conductors, optionally)
Note
The addressing must take place via the cable
end or the M12 connector.
1: AS-i +
2: Aux – (6) (AST...6)
3: AS-i –
4: Aux + (6) (AST...6)
1 4
2 3
R C
S OR
AS-Interface Safety at Work
|
|