AS-Interface Safety at Work
AZM 161 AS Technical data
90
56
M12
5,5
7
18
6
6
6
6
8
29
40
72
16,5
15,8
30
130
104
28
8
26
• Solenoid interlock in 3 versions:
AZM 161 Z ST.-AS:
Release, when door is locked
AZM 161 B ST.-AS:
Release, when door is closed
AZM 161 BZ ST.-AS:
AS-i split code 1, when door is closed
AS-i split code 2, when door is locked
• High holding force 2,000 N
• Integrated AS-Interface
• AS-Interface LED and status display
• AS-Interface M12 connector
• AS-Interface magnet control
• Solenoid power supply via AS-Interface or an
external 24 VDC power supply (suffix P)
• Intelligent diagnosis functions
• Manual release, emergency exit
or emergency release
• Protection class IP 67
Ordering details
Technical data
Ordering details
No. Option Description
Å Manual release
N Emergency release
T Emergency exit
Manual Emergency Emergency
release release exit
AZM 161 À Á-ASÂÃÄÅ
No. Option Description
À Z Interlock monitored
B Actuator monitored
BZ Combined monitoring of
actuator/solenoid interlock
Á ST1 Connector (middle)
ST2 Connector (right)
 Latching force 5 N
R Latching force 30 N
à Power to unlock
A Power to lock
Ä Integrated solenoid supply
from AS-i
P External solenoid supply
24 VDC (Aux)
Magnet: 100% ED
Device fuse: £ 4 A
when used to UL 508
Ambient conditions:
Ambient temperature: – 25 °C … + 60 ºC
Storage and transport
temperature: – 25 °C … + 85 °C
Relative humidity: 30% … 95%,
non-condensing, non-icing
Resistance to vibration: 10 ... 150 Hz,
amplitude 0.35 mm
Resistance to shock: 30 g / 11 ms
Switching frequency f: £ 1 Hz
Switch-off delay: < 100 ms
Actuating speed: £ 2 m/s
Classification: *approvals under
preparation
If a fault exclusion for hazardous damage
of the 1-channel mechanics is authorized
and an adequate protection against tampering
is ensured, suitable for use up to:
Standards: EN ISO 13849-1; IEC 61508
PL: up to d
Category: up to 3
PFH value: 1,01 x 10-7 /h
for max. 100.000 operations/year
SIL: up to 2
Service life: 20 years
Basically suitable up to:
Standards: EN ISO 13849-1; IEC 61508
PL: up to c
Category: up to 1
PFH value: 1,16 x 10-6 /h
for max. 100.000 operations/year
SIL: up to 1
Service life: 20 years
Diagnostic function:
Locking/unlocking of the
solenoid interlock blocked:
This error is detected, when the solenoid interlock
can no longer be correctly locked or
unlocked, for instance due to an incorrectly
closed safety guard, a tilted actuator or an
incorrect reset manual release.
The error is transmitted as “peripheral error”
to the control system through the AS-i Master
and indicated by the alternate flashing of the
red/green AS-i duo-LED on the device.
Note
The solenoid interlock and the actuator unit
must be ordered separately!
Interlocks with power to lock principle may
only be used after a thorough evaluation of the
accident risk, since the safety guard can be
opened immediately on failure of the power
supply or upon activation of the main switch.
The addressing must take place via
the M12 connector.
1: AS-i +
2: Aux – (P)
3: AS-i –
4: Aux + (P)
1 4
2 3
C
Approvals
F* *
* under preparation
Standards: EN 50295, EN 60947-5-1,
EN ISO 13849-1, IEC 61508
Enclosure: glass-fibre reinforced
thermoplastic, self-extinguishing
Actuator and locking bolt: stainless steel
Mechanical life: ³ 1 million operations
Fmax: 2000 N
Holding force: typically 30 N for suffix R
Protection class: IP 67 to IEC/EN 60529
Protection class: II, X
Overvoltage category: III
Degree of pollution: 3
Connection: Connector M12, 4 poles
Electrical data AS-Interface:
Operating voltage: 26.5 ... 31.6 VDC,
via AS-Interface, reverse-polarity proof
Operating current: max. 0,25 A
suffix P: max. 0,1 A
AS-Interface specification:
(V 2.1) Profile S-7.B
IO-Code 0x7
ID-Code 0xB
ID-Code1: 0xF
ID-Code2 0xE
AS-I inputs: Data bits D0 ... D3:
static code 0 or dynamic
code transmission
AS-I outputs:
Bit 0 Solenoid control
Bit 1 ... Bit 3 not used
Parameter port:
P0: Actuator present
P1: Interlock locked
P2: Auxiliary voltage on
P3: Error “locking/unlocking” blocked
Input module address: preset to address 0,
can be modified by means of the
AS-Interface bus master or
the hand programming device
Diagnostic display:
LED yellow Channel 1 / AS-i SaW-Bit 0,1
LED green/red AS-i supply voltage on/
AS-i communication error/
Slave address = 0 or
peripherals error
LED yellow Channel 2 / AS-i SaW-Bit 2,3
Auxiliary voltage (Aux) (suffix P):
Operating voltage: 24 VDC (– 15% / + 10%)
(stabilised PELV)
Operating current: max. 0,5 A
|
|