AS-Interface Safety at Work
The diagnostic function of the AZM 200 solenoid interlock
The operating condition of the solenoid interlock as well as possible failures and faults are signalled by means of three-colour LED’s,
installed to the front of the device.
System condition Solenoid control LED AS-i SaW condition
Bit 0
Power-to- Power-tounlock
lock green/red3) red yellow (D0…D3)
Safety guard open 1 (0) 0 (1) green off off static 0
Safety guard closed, 1 (0) 0 (1) green off off static 0
actuator not inserted
Safety guard closed, 1 0 green off flashes AZM 200 ST-T-AS: static 0
actuator inserted, AZM 200 B ST-T-AS: dynamic
(not locked) AZM 200 BZ ST-T-AS: D0, D1: dynamic
D2, D3: static 0
Safety guard closed,
actuator inserted 0 1 green off on dynamic
and locked
Failure warning1), actuator 0 1 green flashes2) on dynamic
inserted and locked, /on
switch-off approaching
Failure 0 (1) 1 (0) green flashes2) off static 0
Internal error 0 (1) 1 (0) green on off static 0
AS-i Failure:
Slave address = 0 or 1 (0) 0 (1) red Condition- static 0
communication error dependent
1) after 30 min -> failure / internal error
2) refer to flash codes
3) AS-i combination LED (green/red)
Flash codes Meaning Autonomous Cause
(red) switch-off after
4 flash pulses Failure (warning) 30 min Temperature measurement
ambient tempera- indicates too high an inner
turetoo high temperature
5 flash pulses Error target 0 min The coding (frequency) of the
detected actuator does not
match the required value,
incorrect or defective actuator
6 flash pulses Error target 0 min An invalid combination of
combination targets was detected at the
4 coils of the AZM 200 solenoid
interlock. (Current setting:
latching bolt detected & door
target not detected => latch
breakage or tampering attempt)
Continuous Internal failure 0 min –
red
Diagnostic of the solenoid interlock
Power supply
The AZM 200 AS solenoid interlock is powered
by the AS-Interface system. The energy for the
locking solenoids is supplied separately (Aux).
The connection to the AS-Interface system
is realised by means of an M12 connector
with A-coding.
Solenoid control
The control system with the AS-Interface
Master can lock and unlock the solenoid
interlock through output bit DO 0 of the AS-i
slave AZM 200 AS.
Reading the parameter port
Parameter ports P0 to P3 of the solenoid
interlock can be read out through the control
interface of the AS-i master (see component
description) by means of the “Write parameter”
instruction (with hexadecimal value F). This
(non-safe) diagnostic information from the
answer to a “Write parameter instruction” can
be used by the user for diagnostic purposes
or for the control programme.
|
|