18
AZ 200 AS
40
220
155,5
5
6,5
32,5
37,7
7,5
3,3
20 ± 1
M12
• Safety switches with separate actuator
• With integrated guard detection sensor
• Integrated AS-Interface
• AS-Interface LED and status display
• AS-Interface M12 connector
• Sensor technology permits an offset
between actuator and switch of ± 5 mm
• Intelligent diagnosis
• Protection class IP 67
• Suitable for applications:
- up to PL e/category 4 to EN ISO 13849-1
- up to SIL 3 to IEC 61508
AZ 200 ST-T-AS
Technical data
Actuating distances to IEC 60947-5-3:
Rated operating distance Sn: 6.5 mm
Assured operation distance Sao: 4.0 mm
Assured release distance Sar: 30 mm
Hysteresis: max. 1.5 mm
Repeat accuracy R: 1 million operations
Latching force: 30 N
Protection class: IP 67 to IEC/EN 60529
Insulation protection class: II, X
Overvoltage category: III
Degree of pollution: 3
Connection: connector M 12 x 1,
four pole, 4 A
Electrical data:
Operating voltage: 26.5 ... 31.6 VDC,
via AS-Interface,
reverse-polarity proof
Operating current: AS electronics: max. 0.1 A
AS-Interface specification:
(V 2.1) Profile: S-0.B
IO-Code: 0x0
ID-Code: 0xB
ID-Code1: 0xF
ID-Code2: 0xE
Outputs: Data bits D0 ... D3:
static code 0 or dynamic
code transmission
Inputs: none
Parameter port:
P0: Guard and actuator detected
P1: Safety release
P2: Static 0
P3: Error
Input module address: preset to address 0,
can be modified by means of the
AS-Interface bus master or
the hand programming device
Diagnostic display:
LED green/red AS-i supply voltage on/
AS-i communication error/
Slave address = 0
LED yellow Authorisation
LED red Device error
The safety switch and the actuator unit (refer
to page 22/23) must be ordered separately.
R C
S OR
AS-Interface Safety at Work
Ordering details Note Connecting
C
Approvals
F
|
|