1 to 20kVA Modular UPS: A11J
12Pages

{{requestButtons}}

Catalog excerpts

1 to 20kVA Modular UPS: A11J - 2

Highly Reliable and Efcient Online UPS A11J ONLINE UPS UL1778-4th (E226092), CE Input Output 100 V AC single-phase 3-wire Battery backup time 100 V/200 V AC single-phase 2-wire Output capacity or or 200 V AC single-phase 2-wire 5/10 kVA 5min min *1 100 V AC *2 single-phase 2-wire *1 3U type with a load factor of 0.8. *2 4U type with a load factor of 0.75. Optional battery 200 V AC *3 single-phase 2-wire 100 V/200 V AC 200 V AC single-phase 2-wire single-phase 3-wire 5/10/15/20 kVA min or 100 V AC *3 *3 15min 25min 35min 45min min *3 min *3 There are some restrictions on the combination with...

Open the catalog to page 2
1 to 20kVA Modular UPS: A11J - 3

1 High Efciency High 93% efciency (with the 5 kVA single unit model). Reduces running cost and helps conserve energy. Efciency of 93 Commercial power supply Device 2 High Reliability Periodic automatic battery operation tests ensure reliable operation during a power outage. *You can select the frequency of the battery operation test from 1, 3 and 6 months. The factory setting is 6 months. Start operation test Normal operation Commercial power supply Rectier Booster Check battery power supply Inverter Device Periodic check Commercial power supply Rectier Booster Inverter Device Battery...

Open the catalog to page 3
1 to 20kVA Modular UPS: A11J - 4

4 Space-saving Design The compact 3U size of the 5 kVA UPS unit (for 5-minute backup) allows you to mount it in an EIA 19-inch rack. 3U size (130 mm) (5.12 inch) 5 Able to Supply Power to High Power Factor Devices A 0.9 load power factor enables the unit to supply power to high power factor devices such as servers. Output capacity of 5 kVA 4.5 kW max. Output capacity of 20 kVA 18 kW max. UL/CE certified unit: 17 kW max. 6 Easy Maintenance Front removable battery pack and inverter provide easy maintenance. *You can replace the battery pack without interrupting inverter power supply...

Open the catalog to page 4
1 to 20kVA Modular UPS: A11J - 5

External View 5kVA Front 20kVA Front Model: A11J502****T/N Model: A11J203S**** Input LED Backup LED LCD Inverter ON/OFF Switch Warning LED Input LED Output LED Alarm LED Input Switch Menu Operation Switch Inverter ON/OFF Switch Maintenance Bypass Switch (Inside Cover) * This is not available for UL/CE certified units Output LED 5kVA Back Model: A11J502****T Terminal Block Type Optional Battery Connector Output Receptacle (NEMA L6-30R) External Control Terminal (EPO and Remote ON/OFF) Card Interface 20kVA Back Model: A11J203S**** Optional Battery Connector Cooling Fan I/O Connector...

Open the catalog to page 5
1 to 20kVA Modular UPS: A11J - 6

Specication Model A11J502A002T Item Feature A11J502A002N A11J502SA002 Single / Terminal block Rated output capacity (Apparent power/Active power) 5 kVA N unit setting Single / NEMA Plug 5 kVA 4.5 kW A11J103SA002 A11J103A002T 4.5 kW 5 kVA 4.5 kW A11J203SA002 10 kVA 9 kW 15 kVA 13.5 kW 20 kVA 18 kW*7 5 kVA N+1 unit setting 4.5 kW 10 kVA 9 kW 15 kVA Capacity increasable (with 20 kVA Power Distribution Unit) 13.5 kW *2 Power supply system System A11J153SA002 Capacity increasable / Parallel redundantable*1 True online power supply synchronized with commercial power source Cooling system Forced...

Open the catalog to page 6
1 to 20kVA Modular UPS: A11J - 7

Specication Model A11J502WA001 Item Rated output capacity (Apparent power/Active power) N unit setting 5 kVA A11J103WA001 4.5 kW 10 kVA N+1 unit setting 5 kVA A11J502WA002 9 kW 5 kVA 4.5 kW A11J153WA002 A11J203WA002 9 kW 15 kVA 13.5 kW 20 kVA 18 kW 4.5 kW 10 kVA 9 kW 15 kVA 13.5 kW A11J103WA002 4.5 kW 10 kVA 5 kVA Capacity increasable (with 20 kVA Power Distribution Unit) Power supply system True online power supply synchronized with commercial power source Cooling system Forced air cooling Inverter system System High-frequency PWM IEC Standard VFI-SS-111 Rated voltage Rated frequency AC...

Open the catalog to page 7
1 to 20kVA Modular UPS: A11J - 8

Specications of External Connection Terminal, Wiring Wire, etc. Model Backup time 5 min. Backup time 10 min. A11J502A002T A11J502A002T-4U A11J502A002N A11J502A002N-4U Input wire *1 Input: M6 Output: NEMA L6-30R 8 mm2 IEC-C13 ( 2 ) Input: NEMA L6-30P Output: NEMA L6-30R 2 NEMA L6-20R 2 Input: M6 Output: M6 NEMA L6-30R NEMA L6-20R A11J103A002T A11J502SA002 I/O connection terminal/plug Output wire *1 Grounding wire *1 Input breaker capacity *1 8 mm2 5.5 mm2 40 A or more 30 A or more A11J502SA002-4U 22 mm2 22 mm2 14 mm2 80 A or more 8 mm2 2 2 Input Output voltage voltage 8 mm2 8 mm2 40 A or...

Open the catalog to page 8
1 to 20kVA Modular UPS: A11J - 9

External Dimensions Backup Time 5 Minutes, Single Unit/Rack Mounting/Floor Type Model Dimensions Width Size Dipth*1 Height Mass*3 A11J502A002T A11J502A002N Fig.1 435 mm (17.13 in) 700+30 mm (27.56+1.18 in) 130 mm (5.12 in) 61(26) kg [134(57) lbs] Fig.1 435 mm (17.13 in) 700+30 mm (27.56+1.18 in) 130 mm (5.12 in) 61(26) kg [134(57) lbs] Model Dimensions Width Size Dipth*1 Height Mass*3 A11J153SA002 Fig.5 435 mm (17.13 in) 700+80 mm (27.56+3.15 in) 671 mm (26.42 in) 223(118)kg [492(260) lbs] A11J203SA002 A11J502WA001 A11J103WA001 A11J502WA002 Fig.6 Fig.7 Fig.8 Fig.7 435 mm (17.13 in) 435 mm...

Open the catalog to page 9
1 to 20kVA Modular UPS: A11J - 10

External Dimensions Backup Time 10 Minutes, Single Unit/Rack Mounting/Floor Type Model Dimensions Width Size Dipth*1 Height Mass Fig.18 435 mm (17.13 in) 700+30 mm (27.56+1.18 in) 175 mm (6.89 in) 80 kg (176 lbs) A11J502A002N-4U Fig.18 435 mm (17.13 in) 700+30 mm (27.56+1.18 in) 175 mm (6.89 in) 80 kg (176 lbs) A11J502SA002-4U Fig.19 435 mm (17.13 in) 700+80 mm (27.56+3.15 in) 453 mm (17.83 in) 120 kg (265 lbs) A11J103SA002-4U Fig.20 435 mm (17.13 in) 700+80 mm (27.56+3.15 in) 629 mm (24.76 in) 200 kg (441 lbs) A11J153SA002-4U Fig.21 435 mm (17.13 in) 700+80 mm (27.56+3.15 in) 805 mm (31.69...

Open the catalog to page 10
1 to 20kVA Modular UPS: A11J - 11

Battery Box Dimensions, Mass (Rackmounting exclusive use) Battery Board Dimensions, Mass Rack Support Rails Rack mounting dimension A set of left and right rails The figure shows the left rail Rack mounting dimension A set of left and right rails The figure shows the left rail Rack mounting dimension Rack mounting dimension A set of left and right rails The figure shows the left rail This is a rack-mounting transformer unit that can be mounted in a 19-inch rack and that can convert the voltage from 200 V to 100 V. A transformer, a breaker, and a receptacle are integrated into the unit to...

Open the catalog to page 11
1 to 20kVA Modular UPS: A11J - 12

f ^^^r^ Sanyo Denki's ECO PRODUCTS are designed with the concept of lessening impact on the environment in the process from product development to waste.The product units and packaging materials are designed for reduced environmental impact.We have established our own assessment criteria on the environmental impacts applicable to all ECO PRODUCTS processes,ranging from design to manufactureThose products that satisfy the criteria are accredited as ECO PRODUCTS. Notes when investigating use of this product in your applications • Before starting installation, assembling and use, read the...

Open the catalog to page 12

All SANYO DENKI America catalogs and technical brochures

  1. San Ace 40L

    4 Pages

  2. SANMOTION R 3E

    172 Pages

  3. SANMOTION T

    36 Pages

  4. SANMOTION F5

    128 Pages

  5. SANMOTION F2

    84 Pages

  6. SANMOTION C

    12 Pages

  7. DC Fan Catalog

    247 Pages

  8. San Ace 92W

    4 Pages

  9. San Ace B97

    2 Pages

  10. San Ace 40

    2 Pages

  11. San Ace 60T

    2 Pages

  12. Blower

    20 Pages

  13. ACDC Fan

    5 Pages

  14. SANMOTION R

    40 Pages

  15. Hybrid UPS

    8 Pages

Archived catalogs

  1. AC_San_Ace

    56 Pages

  2. DC_San_Ace

    332 Pages

  3. PD-D11A

    8 Pages