FAC P DC ENERGY SYSTEMS

EQUIPMENT connectivity

1. Outgoing distribution. 2. Input protection.

TECHNICAL SPECIFICATIONS

3. MS-102.

MODEL

FAC 1000P FAC 2000PFAC 2700PFAC 5000P 4. FAC P modules.
AC voltage 230 V230 V or 3 x 400 V
5. Slots to upgrade the power. INPUT
Voltage rangePower factor Nominal currentPsophometric noise ± 15%50 / 60 Hz12, 24, 36, 48, 60, 110, 125,216, 220 V
6. Battery protection.
> 0,99
(1)
7. Batteries.
Nominal currentMaximum currentEfficiencyFrequencyProtectionDC nominal voltageVoltage adjustment rangeAccuracyNominal power 24,8 A29,2 A13,5 A15,8 A10,7 A12,6 A5,0 A5,9 A> 87%> 82%> 90%Electronic
8. Input entry cable. 8 1 2 OUTPUT
48, 110, 125 V 12, 24, 36, 48, 60,110, 125, 216, 220 V- 15% + 25% ± 0,1% ( with charged batteries )
(2) (3) 2700 W5000 W
(3) 25, 25, 24, 18, 14,8, 7, 4, 4 A2000 W 75, 75, 48, 36, 29,16, 14, 8, 8 A 49, 22, 20 A 181, 181, 121, 91,72, 40, 36, 20, 20 A
3 4

STRUCTURE
Power factor corrector (PFC)TypeCharging curveCharging current Yes
(1) ProtectionRecharging time Against 5 kV peaks (8 / 20 s )Pb-Ca or Ni-CdI / U constant0,1 to 0,3 C adjustableAgainst overvoltages and undervoltagesIP20
BATTERY 5 6
ProtectionsProtection degree accordingwith the standardsAcoustic noise at 1 metre
GENERALS
Dielectric strengthInsulationStorage temperature 2000 V at 1 minute> 20 M Cooling General alarm Controlled andforcedForced0º C
7
÷ + 40º C2400 m.a.s.l.
(4) ÷ + 70º CUp to 95%, non-condensing100.000 hours15 minutes Mean Time Between Failures (MTBF) 150.000 hours100.000 hoursYes
INDICATORS
NAYesYesYesEN 60950-1RS-232 / RS-485 / relaysYesNAYes Equipment OnBatteries on discharge / floatPortsElectromagnetic compatibility (EMC)
COMMUNICATIONS STANDARDS
Safety EN 61204-3; ETS 300 386-2

OPTIONALS

MarkingManufacturingCEISO 9001 TÜV
Data liable to changes without prior notice.

Monitoring and management unit MS-102.Outgoing distribution. Positive, negative and floating output voltages.Earth fault detector.Any kind of batteries: Sealed, Ni-Cd, wet, etc. Lighting arrestor. Output voltage reducer. Others IP.

(1) Single phase input only.(2) Except 12 V and 24 V output voltages.(3) Except 12 V output voltage.(4) No batteries.

RANGE

RECTIFIER MODULE

DIMENSIONS
(D x W x H mm)
WEIGHT
(Kg)
FAC 1000PFAC 2000P FAC 2700P FAC 5000P
425 x 483 x 2U525 x 483 x 3U
(5)

COMMUNICATIONS & services

450 x 73 x 6U525 x 483 x 4U1215628
(5) 2U for 48V models.

RS-232 and RS-485 serial ports. Relay interface. MODBUS communication protocol.Before and after sales advice service.Multiple maintenance and telemaintenanceformulas.

*

+

902 48 24 00

WWW.SALICRU.COM

34 93 848 24 00

**

AVDA DE LA SERRA 100 · 08460 PALAUTORDERA · SPAIN · FAX +34 93 8481151 REF. JM581A01CODE 401AB000392 ED. JANUARY 2008 SWITCH MODE POWER SUPPLY (*) Spain only (**) Rest of World