CENTERLINE® Motor Control Centers Bulletin 2400 Application-Rated Units
Factory-Installed Options, Modifications, and Accessories, continued
Multiple options are separated by a dash and added to the base catalog number in ascending order.
Option
Option Number
Description
Wiring Type
FVC
FVR
FVNR
2402
2403
2406
2407
2412
2413
Auxiliary Contact
-90
See Options table below
Normally Open
(1) N.O. auxiliary contact mounted on each contactor
A
B [1]
-91 See Options
table
below
Normally Closed
(1) N.C. auxiliary contact mounted on each contactor
A
B [1]
-98 [2]
Normally Open
(1) N.O.
Mounted on operating mechanism (operates with movement of external handle only)
A or B
-98X [3]
Mounted internally Circuit breakers
-99 [2]
Normally Closed
(1) N.C.
Mounted on operating mechanism (operates with movement of external handle only)
-99X [3]
Mounted internally Circuit breakers
[1] Type B auxiliary contacts are wired to terminal blocks. If the number of auxiliary contact wiring points required exceeds the number of terminals available in the unit, remaining auxiliary contacts will be unwired.
[2] The maximum number of auxiliary contacts that can be supplied is two (2), in any combination. Contacts actuate with movement of unit handle to ON or OFF position only. Contacts are not designed to actuate as a result of a circuit breaker trip. If the application requires that the auxiliary contact must indicate state of the circuit breaker power contacts, then the auxiliary contact "mounted internally" (98X or 99X) must be specified. Auxiliary contacts are supplied unwired.
[3] The maximum number of auxiliary contacts that can be supplied internally is two (2) N.O. and (2) N.C. (form C) on F-frame, J-frame, K-frame, and L-frame.
Auxiliary Contact Options (4 = option is available, N/A
= option is not available)
Auxiliary Contact Catalog String
Bulletins 2402, 2403, 2412, and 2413
Bulletins 2406 and 2407
16A-85A Contactors
110A-304A
Contactors
16A-85A Contactors
110A-304A
Contactors
90 [1]
y
y
y
91 [1]
y
y
y
y
900 [1]
y
y
y
901 [1]
y
y
y
911 [1]
y
y
y
9000
y
y
N/A
9001
y
y
N/A
9011
y
y
N/A
9111
N/A
y
N/A
N/A
90000 90001 90011 90111 91111
N/A N/A
y y y y
y y y
N/A N/A
N/A N/A N/A N/A N/A
[1] On 0.5 space factor 2406 and 2407 units with auxiliary contacts (options 90, 91), a maximum of two (2) pilot devices can be specified. If more than two (2) pilot devices are specified, these units will be a minimum of 1.0 space factor.
Publication 2400-CA001B-EN-P—September 2005 31
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42