| | | [1] Use continuous ampere ratings to size for electric discharge loads (fluorescent, mercury vapor, sodium vapor, and metal halogen lamps), tungsten loads, and incandescent lamp loads. Lighting loads are limited to 300V or less. IMPORTANT: Contactors for applications that use a power factor correction capacitor manufacturer on the load (compensated load) must be sized using the information in publication 0100C-1.0.1, MCS Modular Control System, for 30A-60A or publication A11_, Allen-Bradley Industrial Controls, for 100A-300A contactors. For loads containing high harmonic content, consult your local Rockwell Automation Sales Office. [2] The industrial transformers being switched by the contactor must not have inrush currents greater than 20 times the peak continuous current ratings, regardless of the nature of the secondary load. [3] When selecting certain options, a larger space factor may be required than is listed in this table. To determine actual space requirements, see Options section beginning on page 26 and related footnotes. [4] The catalog numbers listed are not complete: • Select the appropriate control voltage code from page 17 to identify the control type desired (e.g., 2403B-C030KBD). • Select the appropriate number from page 17 to identify the trip current (e.g., 2403B-C030KBD-30). • Select the appropriate circuit breaker suffix from page 17 to identify the circuit breaker type (e.g., 2403B-C030KBD-30CT). [5] Units with these ratings are NOT UL listed or cUL certified. | | |