Catalogue Motor Control Centers
www.rockwellautomation.fr
print switch display
Page / 42
ROCKWELL AUTOMATION - 208511, 14318, 80755, 2753, 68303
/ 42
See other catalogues for ROCKWELL AUTOMATION
Text version of the page
CENTERLINE® Motor Control Centers Bulletin 2400 Application-Rated Units
BULLETIN 2403
Combination Full Voltage Contactor with Industrial circuit breaker (FVC)
For unit sizing, select the unit maximum continuous rating (amperes) based upon 125% of actual load amperes. Refer to NEC/CEC.
Max.
Cont. Rating (Amps)
UL/ cUL [1]
Transformer Primary Switching kVA[2]
Space Factor
[3]
Catalog Number [4] Wiring Type B-D—Class I
Delivery Program
220V [5]
230V [5]
240V
380V [5]
400V [5]
415V [5]
480V
600V
NEMA
Type 1/1G
NEMA Type 12
10
30
10
30
10
30
10
30
10
30
10
30
10
30
10
30
30
3.5
6.1
3.5
6.1
3.5
6.1
5.4
9.4
5.4
9.4
5.4
9.4
5.4
9.4
5.4
9.4
0.5
2403B-C030K_-_
2403B-C030J_-_
Engineered
60
6.3
11
6.3
11
6.3
11
11
19
11
19
11
19
11
19
11
19
1.5
2403B-C060K_-_
2403B-C060J_-_
100
11
19
11.5
19.9
12
21
19
33
20
34.7
21
36
24
42
30
52
2.0
2403B-B110K_-_
2403B-B110J_-_
200
21
37
21.9
38.7
23
40
36
63
38
66.3
40
69
46
80
52
90
2.5
2403B-B180K_-_
2403B-B180J_-_
300
29
51
30
53.3
39
67
50
88
53
92.6
55
96
77
134
87
150
3.5
2403B-B250K_-_
2403B-B250J_-_
[1] Use continuous ampere ratings to size for electric discharge loads (fluorescent, mercury vapor, sodium vapor, and metal halogen lamps), tungsten loads, and incandescent lamp loads. Lighting loads are limited to 300V or less.
IMPORTANT: Contactors for applications that use a power factor correction capacitor manufacturer on the load (compensated load) must be sized using the information in publication 0100C-1.0.1, MCS Modular Control System, for 30A-60A or publication A11_, Allen-Bradley Industrial Controls, for 100A-300A contactors. For loads containing high har­monic content, consult your local Rockwell Automation Sales Office.
[2] The industrial transformers being switched by the contactor must not have inrush currents greater than 20 times the peak continuous current ratings, regardless of the nature of the secondary load.
[3] When selecting certain options, a larger space factor may be required than is listed in this table. To determine actual space requirements, see Options section beginning on
page 26 and related footnotes. [4] The catalog numbers listed are not complete:
• Select the appropriate control voltage code from page 17 to identify the control type desired (e.g., 2403B-C030KBD).
• Select the appropriate number from page 17 to identify the trip current (e.g., 2403B-C030KBD-30).
• Select the appropriate circuit breaker suffix from page 17 to identify the circuit breaker type (e.g., 2403B-C030KBD-30CT). [5] Units with these ratings are NOT UL listed or cUL certified.
16 Publication 2400-CA001B-EN-P—September 2005
For Options, Modifications, and Accessories, see page 26
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42