| | | [1] Use continuous ampere ratings to size contactors for electric discharge loads (fluorescent, mercury vapor, sodium vapor, and metal halogen lamps), tungsten loads, and incandescent lamp loads. Lighting loads are limited to 300V or less. IMPORTANT: Contactors for applications that use a power factor correction capacitor manufacturer on the load (compensated load) must be sized using the information in publication 100-SG, MCS Modular Control System, for 30A-60A or publication A113, Allen-Bradley Industrial Controls, for 100A-300A contactors. For loads containing high harmonic content, consult your local Rockwell Automation Sales Office. [2] The transformers being switched by the contactor must not have inrush currents greater than 20 times the peak continuous current ratings, regardless of the nature of the secondary load. [3] When selecting certain options, a larger space factor may be required than is listed in this table. To determine actual space requirements, see Options section beginning on page 26 and related footnotes. [4] The catalog numbers listed are not complete: • Select the appropriate control voltage code from page 15 to identify the control type desired (e.g., 2402B-C030KBD). • Select the appropriate fuse clip designator from page 15 to identify the fuse clip size and type (e.g., 2402B-C030KBD-24J). [5] Units with these ratings are NOT UL listed or cUL certified. | | |