CENTERLINE® Motor Control Centers Bulletin 2400 Application-Rated Units
Bulletin 2402
Combination Full Voltage Contactor with Fusible Disconnect (FVC)
Power fuses are NOT included.
For unit sizing, select the unit maximum continuous rating (amperes) based upon 125% of actual load amperes. Refer to NEC/CEC.
Max.
Cont. Rating (Amps)
UL/ cUL [1]
Transformer Primary Switching kVA [2]
Space Factor
[3]
Catalog Number [4] Wiring Type B-D—Class I
220V [5]
230V [5]
240V
380V [5]
400V [5]
415V [5]
480V
600V
NEMA Type 1/1G
NEMA Type 12
10
30
10
30
10
30
10
30
10
30
10
30
10
30
10
30
30
3.5
6.1
3.5
6.1
3.5
6.1
5.4
9.4
5.4
9.4
5.4
9.4
5.4
9.4
5.4
9.4
0.5
2402B-C030K_-_
2402B-C030J_-_
60
6.3
11
6.3
11
6.3
11
11
19
11
19
11
19
11
19
11
19
1.5
2402B-C060K_-_
2402B-C060J_-_
100
11
19
11.5
19.9
12
21
19
33
20
34.7
21
36
24
42
30
52
2.0
2402B-B110K_-_
2402B-B110J_-_
200
21
37
21.9
38.7
23
40
36
63
38
66.3
40
69
46
80
52
90
2.5
2402B-B180K_-_
2402B-B180J_-_
300
29
51
30
53.3
39
67
50
88
53
92.6
55
96
77
134
87
150
4.0
2402B-B250K_-_
2402B-B250J_-_
Delivery Program
Engineered
[1] Use continuous ampere ratings to size contactors for electric discharge loads (fluorescent, mercury vapor, sodium vapor, and metal halogen lamps), tungsten loads, and in­candescent lamp loads. Lighting loads are limited to 300V or less.
IMPORTANT: Contactors for applications that use a power factor correction capacitor manufacturer on the load (compensated load) must be sized using the information in publication 100-SG, MCS Modular Control System, for 30A-60A or publication A113, Allen-Bradley Industrial Controls, for 100A-300A contactors. For loads containing high harmonic content, consult your local Rockwell Automation Sales Office.
[2] The transformers being switched by the contactor must not have inrush currents greater than 20 times the peak continuous current ratings, regardless of the nature of the secondary load.
[3] When selecting certain options, a larger space factor may be required than is listed in this table. To determine actual space requirements, see Options section beginning on
page 26 and related footnotes. [4] The catalog numbers listed are not complete:
• Select the appropriate control voltage code from page 15 to identify the control type desired (e.g., 2402B-C030KBD).
• Select the appropriate fuse clip designator from page 15 to identify the fuse clip size and type (e.g., 2402B-C030KBD-24J). [5] Units with these ratings are NOT UL listed or cUL certified.
14 Publication 2400-CA001B-EN-P—September 2005
For Options, Modifications, and Accessories, see page 26
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42