| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | Bulletin 2193M Bulletin 2100 CENTERLINE motor control centers are rated for use with 75°C wire. Wire must be sized using the 75°C column in NEC/UL/cUL. The actual temperature rating of the lug is not relevant. Top- and bottom-mounted mains are designed with adequate space to route cables to lugs. Special consideration may need to be given to the mounting of the CT's for a metering device. Addition of a pull box might be considered. Refer to Appendix for wire size conversion table. | | | | | | | | | | Trip Current | | | | | | | | | | | | | | | | | | | Number | Trip Current (Amperes) | Number | Trip Current (Amperes) | | | | 30 | 15 | 45 | 225 | | | | 31 | 20 | 46 | 250 | | | | 32 | 30 | 48 | 300 | | | | 34 | 40 | 49 | 350 | | | | 35 | 50 | 50 | 400 | | | | 36 | 60 | 51 | 500 | | | | 37 | 70 | 52 | 600 | | | | 38 | 80 | 53 | 700 | | | | 39 | 90 | 54 | 800 | | | | 40 | 100 | 55 | 1000 | | | | 41 | 125 | 56 | 1200 | | | | 42 | 150 | 58 | 1600 | | | | 43 | 175 | 60 | 2000 | | | | 44 | 200 | | — | | | | | | | | | | | | | | | ■ | | | | | | | | | | | | | Standard Mechanical Lugs Supplied [1] | | | | | | | | | | | | | | | | | | | | | Frame Type | Rating (Amperes) | Trip Current (Amperes) | Cables/ Phase [2] | Cable/Wire Size Range | Wire Type | | | | FDB, FD, HFD, FDC, FDB-LFD | 150A | 15-100 125-150 | | #14-#1/0 AWG #4- #4/0 AWG | CU/AL CU | | | | JD, HJD, JDC | 225A | 70-225 | | #4-350 kcmil | CU | | | | KD, HKD, KDC | 400A | 125-225 250-350 400 | 2 | #3-350 kcmil 250-500 kcmil #3/0-250 kcmil | CU CU CU | | | | LD, HLD, LDC, LDG, HLDG, LDCG | 600A | 300-600 | 2 | 250-350 kcmil | CU | | | | LD HI-MAG | 600A | 600 | 2 | 250-350 kcmil | CU | | | | MDL, MDLG HMDL, HMDLG | 800A | 400-600 700-800 | 2 3 | #2/0-500 kcmil #3/0-300 kcmil | CU CU | | | | MDL HI-MAG | 800A | 800 | 3 | #3/0-300 kcmil | CU | | | | NDC, NDCG | 800A | 400-700 800 | 2 3 | #2/0-500 kcmil #3/0-500 kcmil | CU CU | | | | ND HI-MAG | 1200A | 1200 | 4 | #3/0-400 kcmil | CU | | | | ND, HND, NDC, NDG, HNDG, NDCG | 1200A | 600-700 800-1000 1200 | 2 3 4 | #2/0-500 kcmil #3/0-500 kcmil #3/0-400 kcmil | CU CU CU | | | | RD, RDG | 2000A | 1200-1600 2000 | 4 6 | #1-600 kcmil #2-600 kcmil | CU CU/AL | | | | ND, HND, NDC, NDG, HNDG, NDCG—100% rated | 1200A | 600-1200 | 4 | #4/0-600 kcmil | CU/AL | | | | | | | | | | | | | | | | | | | | | [1] Lugs are designed for use with breaker frame. See page 78 for additional lugs. [2] If optional full-rated incoming neutral bus (see page 111) is specified, the quantity and size/type of the lug(s) on neutral lug pad will be the same as the 3-phase lugs. When optional half-rated incoming neutral bus (see page 111) is specified and (1) or (2) lugs per phase are specified, (1) lug will be provided on the half-rated neutral riser. When (3) or (4) lugs are specified, (2) lugs will be provided. When (5) or (6) lugs are specified, (3) lugs will be provided on half-rated neutral riser. | | | | | | | | | | For Options, Modifications, and Accessories, see pages 101-117 77 | | | | | | | | | | | | | | | | | | | | | | | | | |
|