Main and Feeder units
Bulletin 2193M
3-Pole Main Industrial circuit breaker (MCB), continued
Bulletin 2100 CENTERLINE motor control centers are rated for use with 75°C wire. Wire must be sized using the 75°C column in NEC/UL/cUL. The actual temperature rating of the lug is not relevant.
Top- and bottom-mounted mains are designed with adequate space to route cables to lugs. Special consideration may need to be given to the mounting of the CT's for a metering device. Addition of a pull box might be considered. Refer to Appendix for wire size conversion table.
Trip Current
Number
Trip Current
(Amperes)
Number
Trip Current
(Amperes)
30
15
45
225
31
20
46
250
32
30
48
300
34
40
49
350
35
50
50
400
36
60
51
500
37
70
52
600
38
80
53
700
39
90
54
800
40
100
55
1000
41
125
56
1200
42
150
58
1600
43
175
60
2000
44
200
Standard Mechanical Lugs Supplied [1]
Frame Type
Rating
(Amperes)
Trip Current
(Amperes)
Cables/ Phase [2]
Cable/Wire Size Range
Wire Type
FDB, FD, HFD, FDC, FDB-LFD
150A
15-100 125-150
#14-#1/0 AWG #4- #4/0 AWG
CU/AL CU
JD, HJD, JDC
225A
70-225
#4-350 kcmil
CU
KD, HKD, KDC
400A
125-225
250-350
400
2
#3-350 kcmil 250-500 kcmil #3/0-250 kcmil
CU CU
CU
LD, HLD, LDC, LDG, HLDG, LDCG
600A
300-600
2
250-350 kcmil
CU
LD HI-MAG
600A
600
2
250-350 kcmil
CU
MDL, MDLG
HMDL, HMDLG
800A
400-600
700-800
2 3
#2/0-500 kcmil
#3/0-300 kcmil
CU CU
MDL HI-MAG
800A
800
3
#3/0-300 kcmil
CU
NDC, NDCG
800A
400-700 800
2 3
#2/0-500 kcmil #3/0-500 kcmil
CU CU
ND HI-MAG
1200A
1200
4
#3/0-400 kcmil
CU
ND, HND, NDC, NDG, HNDG, NDCG
1200A
600-700
800-1000
1200
2 3 4
#2/0-500 kcmil #3/0-500 kcmil #3/0-400 kcmil
CU CU CU
RD, RDG
2000A
1200-1600 2000
4
6
#1-600 kcmil #2-600 kcmil
CU
CU/AL
ND, HND, NDC, NDG, HNDG, NDCG—100% rated
1200A
600-1200
4
#4/0-600 kcmil
CU/AL
[1] Lugs are designed for use with breaker frame. See page 78 for additional lugs.
[2] If optional full-rated incoming neutral bus (see page 111) is specified, the quantity and size/type of the lug(s) on neutral lug pad will be the same as the 3-phase lugs. When optional half-rated incoming neutral bus (see page 111) is specified and (1) or (2) lugs per phase are specified, (1) lug will be provided on the half-rated neutral riser. When (3) or (4) lugs are specified, (2) lugs will be provided. When (5) or (6) lugs are specified, (3) lugs will be provided on half-rated neutral riser.
For Options, Modifications, and Accessories, see pages 101-117 77
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 51 p.51
page 52 p.52
page 53 p.53
page 54 p.54
page 55 p.55
page 56 p.56
page 57 p.57
page 58 p.58
page 59 p.59
page 60 p.60
page 61 p.61
page 62 p.62
page 63 p.63
page 64 p.64
page 65 p.65
page 66 p.66
page 67 p.67
page 68 p.68
page 69 p.69
page 70 p.70
page 71 p.71
page 72 p.72
page 73 p.73
page 74 p.74
page 75 p.75
page 76 p.76
page 77 p.77
page 78 p.78
page 79 p.79
page 80 p.80
page 81 p.81
page 82 p.82
page 83 p.83
page 84 p.84
page 85 p.85
page 86 p.86
page 87 p.87
page 88 p.88
page 89 p.89
page 90 p.90
page 91 p.91
page 92 p.92
page 93 p.93
page 94 p.94
page 95 p.95
page 96 p.96
page 97 p.97
page 98 p.98
page 99 p.99
page 100 p.100
Pages:
1-50
51-100
101-150
151-200
201-250
251-266
pdf-page pdf di En 2008-12-49-02