Catalogue CENTERLINE® Motor Control Centers
www.rockwellautomation.fr
print switch display
Page / 266
Contact the
Manufacturer
Where to buy
this product ?
Request
a Quote
ROCKWELL AUTOMATION - 14318, 68730, 160150
/ 266
See other catalogues for ROCKWELL AUTOMATION
Text version of the page
Main and Feeder units
Bulletin 2193F
3-Pole Feeder Industrial circuit breaker (FCB), continued
• Bulletin 2100 CENTERLINE industrial motor control centers are rated for use with 75° C wires. Wire must be sized using the 75° C column in NEC Table 310-16. The actual temperature rating of the lug is not relevant.
• Refer to Appendix for wire size conversion table.
Trip Current
Standard Mechanical Lugs Supplied [1]
Number
Trip Current
(Amperes)
Number
Trip Current
(Amperes)
00 [1]
(No breaker)
43
175
30
15
44
200
6 31
20
45
225
32
30
46
250
34
40
48
300
35
50
49
350
36
60
50
400
37
70
51
500
38
80
52
600
39
90
53
700
40
100
54
800
41
125
55
1000
42
150
56
1200
Frame Type
Rating
Trip Current
(Amperes)
Cables/ Phase
Cable/Wire Size Range
Wire Type
FDB, FD, HFD, FDC
150A
15-100 125-150
#14-#1/0 AWG #4-#4/0 AWG
CU/AL
FDB-LFD [2]
150A
15-70 80-150
#14-#2 AWG #1-#4/0 AWG
CU/AL CU/AL
JD, HJD, JDC
225A
70-225
#4-350 kcmil
CU/AL
KD, HKD, KDC
400A
125-225 250-350 400
2
#3-350 kcmil 250-500 kcmil
#3/0-250 kcmil
CU CU CU
LD, HLD, LDC
600A
300-600
2
250-350 kcmil
CU
MDL HMDL
800A
400-600 700-800
2 3
#2/0-500 kcmil #3/0-300 kcmil
CU CU
NDC
800A
400-700 800
2 3
#2-500 kcmil #3/0-500 kcmil
CU CU
ND, HND, NDC
1200A
600-700 800-1000 1100-1200
2
3 4
#2/0-500 kcmil #3/0-500 kcmil #4/0-400 kcmil
CU CU CU
[1] Provision for Field Mounting
Single or dual mounted plug-in feeder units may be selected without the circuit breaker in the 150A frame size only. Add the number 00 from Trip Current table above to the base catalog number (e.g., 2193F-AKC-3500CB or 2193F-BKC-4100CB). Mounting hardware, space, and operating mechanism will be provided for future mounting of circuit breaker(s).
[1] Lugs are designed for use with breaker frame. Standard crimp or
mechanical lugs cannot be used without special lug pad assembly. [2] No optional lugs available for FDB frame with current limiters.
Optional Mechanical Lugs [1]
Frame
Type
Rating
Trip Current
(Amperes)
Cables/ Phase
Cable/Wire
Size Range
Wire Type
Option Number
FDB, FD, HFD, FDC
150A
15-100
1
#4-#4/0 AWG
CU/AL
-80A4X0
JD, HJD, JDC
225A
70-225
1
#4-350 kcmil
CU/AL
-80A350
125-225, 400
1
250-500 kcmil
CU
-81A500
125-225
1
#3-350 kcmil
CU/AL
-80A350
KD, HKD, KDC
400A
125-350
2
#3/0-250 kcmil
CU
-81B250
125-400
1
2
250-500 kcmil
#3/0-250 kcmil
CU/AL
-80A500 -80B250
LD, HLD, LDC
600A
300-600
2 2
250-350 kcmil 400-500 kcmil
CU/AL
-80B350 -80B500
MDL HMDL
800A
400-600 400-600 400-800 400- 800
2
3
2 [2]
3
#1-500 kcmil
#3/0-300 kcmil 500-750 kcmil #3/0-400 kcmil
CU/AL CU
CU/AL CU/AL
-80B500 -81C300 -80B750 -80C400
NDC
800A
400-700 400-800
2 3
#1-500 kcmil
#3/0-400 kcmil
CU/AL CU/AL
-80B500 -80C400
ND, HND, NDC
1200A
600-700 600-1000 600-1200 600-1200
2
3 4
3
#1-500 kcmil
#3/0-400 kcmil #4/0-500 kcmil 500-750 kcmil
CU/AL CU/AL CU/AL CU/AL
-80B500 -80C400 -80D500 -80C750
[1] Lugs are designed for use with breaker frame. Standard crimp or mechanical lugs cannot be used without special lug pad assembly.
[2] Requires top entry and pullbox for 600-750 kcmil cables in order to meet UL and NEC/UL/cUL wire bending requirements. Select pullbox on page 26.
74 For Options, Modifications, and Accessories, see pages 101-117
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 51 p.51
page 52 p.52
page 53 p.53
page 54 p.54
page 55 p.55
page 56 p.56
page 57 p.57
page 58 p.58
page 59 p.59
page 60 p.60
page 61 p.61
page 62 p.62
page 63 p.63
page 64 p.64
page 65 p.65
page 66 p.66
page 67 p.67
page 68 p.68
page 69 p.69
page 70 p.70
page 71 p.71
page 72 p.72
page 73 p.73
page 74 p.74
page 75 p.75
page 76 p.76
page 77 p.77
page 78 p.78
page 79 p.79
page 80 p.80
page 81 p.81
page 82 p.82
page 83 p.83
page 84 p.84
page 85 p.85
page 86 p.86
page 87 p.87
page 88 p.88