Contactor and Starter Units
Bulletin 2173
Closed Transition Reduced Voltage Autotransformer Type Starter Unit with Circuit Breaker (RVAT)
See page 32 for product description.
Autotransformers (<200 Hp) allow a starting time of 10, 15, or 25 seconds (at 80%, 65%. or 50% TAPS, respectively) out of each four minutes for one hour, followed by a rest period of two hours. Autotransformers > 200 Hp allow a starting time of 20, 30, or 50 seconds (at 80%, 65%, or 50% TAPS, respectively). This is followed by an off time of 30 seconds for a maximum of three starts, followed by a rest period of one hour. If starting times are excessive, contact your local Rockwell Automation Sales Office. Duty cycle may be changed or components may have to be changed or added. See NEC Article 430. Both interposing relay and incomplete starting sequence protection are provided as standard. Standard factory settings are underlined.
NEMA
Line Voltages
Space
Catalog Number [1] Wiring Type B—Class I
Delivery
Size
240V Hp
480V/600V
Hp a
Factor
NEMA Type 1 and Type 1 w/ gasket
NEMA Type 12
Program
2
10-15
15-25
3.5
2173B-CA_-_
2173B-CD_-_
3
20-30
30-50
4.5
2173B-DA_-_
2173B-DD_-_
4 [3]
40-50
60-100
6.0
2173B-EA_-_
2173B-ED_-_
PE-II
5 [3]
60-100
125-200
6.0, 25" W
2173B-FA_-_
2173B-FD_-_
6 [3],[4],[5]
125-200
250-400
6.0, 35" W 20" D [6]
2173B-GA_-_
2173B-GD_-_
[1] The catalog numbers listed are not complete:
• Select the control voltage type from table on page 205 (e.g., 2173B-EABD).
• Select the horsepower from table on page 206 (e.g., 2173B-EABD-48).
• Select the circuit breaker type from table on page 211 (e.g., 2173B-EABD-48CA).
• For circuit breaker size based on load horsepower, refer to publications 2100-TD001x-EN-P and 2100-TD002r-EN-P.
The catalog numbers listed include an external reset button for the overload relay. To order catalog numbers without the external reset button, replace the letter
"A" for the letter "K" (e.g., 2173B-BK_-_) or replace the letter "D" with the letter "J" (e.g., 2173B-BJ_-_).
[2] Delivery program is PE-II in United States and SC-II in Canada for 600V and SC-II in United States and PE-II in Canada for 480V. [3] Available with Type B wiring only.
[4] Vertical section contains horizontal power bus that is mounted 5" deeper than standard. A special bus splice kit is provided when a NEMA size 6 starter is
selected adjacent to a standard 20" deep vertical section. Not available in NEMA Type 3R, Type 4, or back-to-back construction. [5] For 200 Hp at 240V or 400 Hp at 480V, suffix letter identifying circuit breaker must be CT or CM only. [6] Frame mounted 20" deep section without vertical wireway. Horizontal bus is 5" deeper than standard.
For Options, Modifications, and Accessories, see pages 101-117 53
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 51 p.51
page 52 p.52
page 53 p.53
page 54 p.54
page 55 p.55
page 56 p.56
page 57 p.57
page 58 p.58
page 59 p.59
page 60 p.60
page 61 p.61
page 62 p.62
page 63 p.63
page 64 p.64
page 65 p.65
page 66 p.66
page 67 p.67
page 68 p.68
page 69 p.69
page 70 p.70
page 71 p.71
page 72 p.72
page 73 p.73
page 74 p.74
page 75 p.75
page 76 p.76
page 77 p.77
page 78 p.78
page 79 p.79
page 80 p.80
page 81 p.81
page 82 p.82
page 83 p.83
page 84 p.84
page 85 p.85
page 86 p.86
page 87 p.87
page 88 p.88
page 89 p.89
page 90 p.90
page 91 p.91
page 92 p.92
page 93 p.93
page 94 p.94
page 95 p.95
page 96 p.96
page 97 p.97
page 98 p.98
page 99 p.99
page 100 p.100
Pages:
1-50
51-100
101-150
151-200
201-250
251-266
pdf-page pdf di En 2008-12-49-02