Contactor and Starter Units
Bulletin 2102L
Full Voltage Lighting Contactor Unit with Fusible Disconnect switch (FVLC)
• See page 31 for product description.
• For unit sizing, select unit rating based on 125% of actual load amperes.
Note: In order to address the heating effects from loads containing a high degree of harmonic content, it may be necessary to oversize the field conductors (especially neutrals), use k-factor lighting industrial transformers, and oversize the lighting contactor units (increase by 50%); for high harmonic load applications, Contact your local Rockwell Automation Sales Office.
Rating
(Amperes) [1]
Transformer Primary Switching kVA [2]
Fuse Clip (See Appendix for
short circuit withstand ratings.)
Space Factor
Catalog Number [3] Wiring Type B—Class I
Delivery Program
208V
240V
380V-415V
480V
600V
NEMA Type 1 and Type 1 w/ gasket
NEMA Type 12
10
30
10
30
10
30
10
30
10
30
Rating
(Amperes)
Class
30[4]
1.2
3.6
2.4
4.3
2.8
7.1
4.9
8.5
6.2
11
30
CC, J
0.5
2102LB-ZK_-_
2102LB-ZJ_-_
SC
30
1.2
3.6
2.4
4.3
2.8
7.1
4.9
8.5
6.2
11
30
CC, J,
R, H
1.0
2102LB-BK_-_
2102LB-BJ_-_
60
2.1
6.3
4.1
7.2
6.8
11.8
8.3
14
10
18
30 60
J, R, H
1.0
2102LB-CK_-_
2102LB-CJ_-_
100
4.1
12
8.1
14
13.3
23.3
16
28
20
35
60 100
J, R, H
2.5
2102LB-DK_-_
2102LB-DJ_-_
200
6.8
20
14
23
22.5
39
27
47
34
59
100 200
J, R, H
3.0
2102LB-EK_-__
2102LB-EJ_-__
300
14
41
27
47
45
78.3
54
94
68
117
200 400
J, R, H
4.0
2102LB-FK_-__
2102LB-FJ_-__
[1] Ampere ratings apply to non-motor loads such as fluorescent ballasts, mercury vapor lamps, and resistive heating. Tungsten lamp current ratings are limited to
applications 480 volts line-to-line (277 volts line-to-neutral) maximum. [2] Ratings are based on the contactor being used to switch transformers having an inrush of not more than 20 times their rated full load current, regardless of the
nature of the secondary load. Ratings do not apply to transformers used in resistance welder manufacturer service. [3] The catalog numbers listed are not complete:
• Select control voltage type from table on page 205 (e.g., 2102LB-BKBD).
• Then select designator from table on page 208 (e.g., 2102LB-BKBD-24J).
• To select optional power fuse, select from table on page 208 (e.g., 2102LB-BKBD-24J-607G).
• For fuse rating, based on disconnect rating see publication 2100-TD003x-EN-P.
[4] Separate or transformer control only, except 208V (where separate control only). These units have horizontal handles, Bulletin 194R fused molded case switch, up to three (3) Bulletin 800E pilot devices, and one (1) 7-pt. pull-apart control terminal block with #16 AWG control wire only. One (1) 3-pole power terminal block is supplied as standard.
34 For Options, Modifications, and Accessories, see pages 101-117
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42
page 43 p.43
page 44 p.44
page 45 p.45
page 46 p.46
page 47 p.47
page 48 p.48
page 49 p.49
page 50 p.50
Pages:
1-50
51-100
101-150
151-200
201-250
251-266
pdf-page pdf di En 2008-10-42-14