PIR6WT-1Z

interface - time relays 17

•9-functions electronic time relays• Time relay PIR6WT-1Z consists of:- universal socket with electronic PI6WT-1Z with screw terminals,- changeover relay RM699V , rated load 6 A / 230 V (AC1) or solid state relay RSR30 • 35 mm DIN rail mount, EN 50022 • Adapted for the co-operationwith interconnection strip type ZG20 • Equipped in LED green• Recognitions, certifications, directives:
Type of relay PIR6WT-1Z

Output circuit (RM699V) - contact data

Number and type of contacts (code of output) 1 NO - normally open (R) Contact material AgSnO
2 Max. switching voltageAC/DC 250 V / 300 V Min. switching voltageAC/DCRated loadAC1 12 V6 A / 230 V AC DC1 6 A / 24 V DC Min. switching current 100 mA Max. inrush current 15 A
20 ms Rated current 6 A Max. breaking capacityAC1 1 500 VA Min. breaking capacity 1 W Contact resistance Max. operating frequency • at rated loadAC1 100 m
100 mA, 24 V 360 cycles/hour • no load 72 000 cycles/hour

Output circuit (RSR30) - output data

Type of output (code of output) Triac (T)Transistor (C)Transistor (O) 240 V / 2 A48 V / 1 A24 V / 2 A Number and type of outputs 1 NO - normally open1 NO - normally open1 NO - normally open Rated voltage 240 V AC48 V DC24 V DC Max. output voltage 280 V AC60 V DC32 V DC Min. output voltage Rated continuous output currentAC1 12 V AC1,5 V DC1,5 V DC1 A / 240 V AC DC1 1 A / 60 V DC2 A / 60 V DC Min. making capacity current 50 mA1 mA1 mA Max. off-state leakage current
(rest condition) 1,5 mA1 mA1 mA Output rated current 1 A1 A2 A
Max. on-state voltage drop on the connection (operating state) 1,2 V0,4 V0,24 V Operating switching frequency 10 Hz10 Hz

Input control circuit

Rated voltage
AC: 50/60 Hz AC/DC 12- 24 V Operating range of supply voltage 0,9...1,2 U
n 12 V AC/DC 0,85...1,2 U
n 24 V AC/DC Rated power consumptionAC/DC 0,5 VA / 0,5 W
12 V AC/DC 1,0 VA / 1,0 W
24 V AC/DC Range of supply frequencyControl contact (A3) S
AC: 48...100 Hzbetween terminals (A3) S and A1 • control voltage • min. voltage 8 V • min. time of pulse duration 15 ms

Insulation

Insulation category B250 Insulation rated voltage 250 V AC Rated surge voltage 2 500 V AC Overvoltage category II
PN-EN 60664-1 Insulation pollution degree 2 Flammability degree Dielectric strength• input - output
contact plate: V-0
cover: V-1
UL94 2 500 V AC
50/60 Hz, 1 min. • contact clearance 1 000 V AC
50/60 Hz, 1 min., output R The data in bold type pertain to the standard versions of the relays. Characteristics of the contact capacity of relays PIR6WT-1Z with RM699V - see catalogue Relpol S.A. ”Electromagnetic relays ”, pages 49-51; PIR6WT-1Z with RSR30 - see catalogue Relpol S.A. ”Solid state relays”, pages 10-14. Control contact (A3) S is activated by connecting it to A1 terminal. Where the control signal is recognizable. Dzia³ Marketingu Tel./Fax +48 68 47 90 830 • Wsparcie Techniczne Tel. +48 68 47 90 820 www.relpol.com.pl