Stand
Group: Spectris plc

CUB7 - 8 Pages

1
1.64 (41.6)
0.87
(22.1)
1.10
(27.9)
2.00 (50.8) 2.17 (55)
With Wires With Terminal Block
Ć 0.35" (8.9 mm) HIGH LCD DIGITS, REFLECTIVE OR TRANSMISSIVE
WITH YELLOW/GREEN OR RED BACKLIGHTING (6-26 VDC power
supply required for version with LED backlighting)
Ć INTERNAL LITHIUM BATTERY PROVIDES UP TO 7 YEARS OF
TYPICAL UNINTERRUPTED OPERATION
Ć COUNT SPEEDS UP TO 10KHZ
Ć 9 PROGRAMMABLE TIME RANGES
Ć CONTACT, LOGIC, OPEN COLLECTOR, OR HIGH VOLTAGE INPUTS
Ć STANDARD WIRE CONNECTIONS OR OPTIONAL PLUG-IN TERMINAL
BLOCK
Ć NEMA 4X/IP65 SEALED FRONT BEZEL THAT FITS 1/32 DIN CUT-OUT
DESCRIPTION
The CUB7 series is an 8-digit lithium battery powered miniature counter or
timer with large 0.35" (8.9 mm) high digits. It has an LCD read-out available in
Positive Imagine Reflective, Negative Image Transmissive with yellow/green or
red backlighting. The backlight versions require an external 6-26 VDC power
supply. The CUB7 series is housed in a lightweight, high impact plastic case
with a clear viewing window. The sealed front panel with silicon rubber keypad
meets NEMA 4X/IP65 specification for wash-down and/or dusty environments,
when properly installed with supplied panel gasket and mounting clip.
Both counter and timer CUB7 models are available with a low voltage input
(28 VDC max) or an isolated high voltage input (50-250 VDC/VAC). The low
voltage input has DIP switch selections for SINKING or SOURCING along
with a HIGH/LOW FREQUENCY selection (low frequency for contact inputs).
Both units have front panel keypads that can be used to reset the display. The
keypad can be enabled/disabled via a single DIP switch. The standard unit uses
22 gauge wires for external connections, an optional plug-in terminal block is
available.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
1. DISPLAY: 8-digit LCD, 0.35" (8.90 mm) high digits
2. POWER: Non-replaceable internal 3.6 VDC lithium battery provides 7 years
of typical continuous operation (high count speeds in SNK mode & extreme
ambient temperatures will decrease battery life, use of SRC mode can extend
battery life)
OPTIONAL LED BACKLIGHT POWER: 6-26 VDC @ 25 mA max.
3. LOW VOLTAGE INPUT:
COUNTERS: CUB7CCS0, CUB7CCR0, CUB7CCG0
SNK mode (DIP switch 1 off, internal pull-up to battery)
VIN High Min = 1.25 VDC; VIN Low Max = 0.45 VDC
IIN Max = 5 ìA; VIN Max = 3.6 VDC
Count Speed: (count on negative edge)
High freq mode (DIP switch 2 off): max 5 kHz @ 50% duty cycle
Low freq mode (DIP switch 2 on): max 50 Hz @ 50% duty cycle
Note: The three models listed above may be used for count inputs with
10-50 VAC signals when using a VCM10000 converter module. DIP
switches must be set for SNK and Low frequency.
SRC mode (DIP switch 1 on, internal 20 kĂ pull-down to common)
VIN High Min = 1.25 VDC; VIN Low Max = 0.45 VDC
IIN Max = 5 mA; VIN Max = 28 VDC
Count Speed: (count on negative edge)
High freq mode (DIP switch 2 off): max 10 kHz @ 50% duty cycle
Low freq mode (DIP switch 2 on): max 500 Hz @ 50% duty cycle
TIMERS:
Models: CUB7TCS0, CUB7TCR0, CUB7TCG0 For these models, the
unit will time when the CUB7 input is low.
SNK mode (DIP switch 1 off, internal pull-up to battery)
VIN High Min = 1.25 VDC; VIN Low Max = 0.45 VDC
IIN Max = 5 ìA; VIN Max = 3.6 VDC
Note: The three models listed above may be used with 10-50 VAC
signals when using a VCM10000 converter module.
SRC mode (DIP switch 1 on, internal 20 kĂ pull-down to common)
VIN High Min = 1.25 VDC; VIN Low Max = 0.45 VDC
IIN Max = 5 mA; VIN Max = 28 VDC
MODEL CUB7 – MINIATURE ELECTRONIC 8 DIGIT COUNTER or TIMER
DIMENSIONS In inches (mm) Note: Recommended minimum clearance (behind the panel) for
mounting clip installation is 2.1" (53.4) H x 5.5" (140) W.
Bulletin No. CUB7N-B
Drawing No. LP0825
Released 07/10
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.

CUB7
  1. P. 1

  2. P. 2

    2ORDERING INFORMATIONAccessories Part NumbersTYPE DESCRIPTION PART NUMBER USED WITHPlug-inTerminal Block3 Position Terminal Block TB100003 CUB7CCS0, CUB7TCS0,...
  3. P. 3

    31.0 INSTALLING THE METERINSTALLATION ENVIRONMENTThe unit should be installed in a location that does not exceed the maximumoperating temperature and provides...
  4. P. 4

    44.0 RESETTING THE DISPLAYThe display may be reset to zero via the front RST key, the remote reset inputor both.The front RST key must be enabled for front...
  5. P. 5

    55.0 WIRING THE METERWIRING OVERVIEWElectrical connections are made to the #22 AWG colored wires protrudingfrom the rear of the unit. When using the optional...
  6. P. 6

    6SRCLO FREQKEY DIS KEY ENHI FREQ1 2SNKON*3LV INPUT1RESET+BACKLIGHTPOWERCOMMON2 3 4OptionalBacklightPower+-SRCLO FREQKEY DIS KEY ENHI FREQ1 2SNK ON*31 2...
  7. P. 7

  8. P. 8

Text version

All Red Lion Controls catalogues and technical brochures

  1. PAX2A Data Sheet

    2 Pages

    En
  2. Panel meter

    5 Pages

    En

Archived catalogues

  1. LD

    16 Pages

    En
  2. CUB4L

    4 Pages

    En
  3. GEMINI 52

    8 Pages

    En
  4. CUB5

    16 Pages

    En
  5. EPAX/MPAX

    8 Pages

    En
  6. PAXLCR

    12 Pages

    En
  7. PAXI

    32 Pages

    En
  8. LPAX/MPAX

    4 Pages

    En
  9. LEGEND

    8 Pages

    En
  10. GEMINI 1 & 2

    8 Pages

    En
  11. C48C

    6 Pages

    En