TECHNOLOGY
Wiring of the
inductive sensors should be routed separately or screened from heavy conductor lines, asin extreme cases inductive peak voltages can destroy the sensors despite the integrated protective circuit.
Screened cable or twisted lines are recommended, especially for longer cable runs > 5 m. Direct control of
electric light
industrial bulbs is to be avoided, because during the switch-on moment cold current is many times the
rated current and can destroy the output stage of the sensor. Units with strong local fields , e. g. high power walkie-talkies, or noise sources in the lower frequencyrange, e.g. long, middle or short wave transmitters should not be operated close to the sensors or addi-
tional measures have to be taken in order to eliminate their maloperation.2- and 3-wire sensors with binary output can be used in series or parallel connection, similar to mechanicalcontacts. The type-typical voltage drop and the residual voltage U >
d , which must be multiplied in accordancewith the number of sensors for series connection, must be noted. In the case of parallel connection of
sensors with thyristor output, the first switched output takes over the total load current. >
Series connectionParallel connection
2 wire AC/DC
3 wire DC NPN
3 wire DC PNP >