You may also be interested in
Filter, Core, Three-phase choke, Three-phase filter, Filter connector
Text version of the page
RP425 Series 3-Phase Wye Dual Stage Power Line Filter RP4253PH WYE TO 300AROHS COMPLIANTSpecificationsOperating Frequency: DC - 60Hz Operating Voltage: 480V +10% Ambient Temperature: 50o C Inrush Rating: 20x (10ms), 1.5x (1min) Climatic Category: 25/100/21 Leakage CurrentHipot Rating : 3000VDC (P/N - E) Ycap, nF mA, 400V/50HZ Terminations: 15/30/50A (M5), 80/100A (M6), 150/200A (M10), 300A (M12) 0 0 .22 .004 Safety Approval: UR/CSA/EN133200 .47 .009 1 .018 2.2 .04 3.3 .06Part Number/Ordering4.7 .09 RP425 -X (Amps) -Y(Y-cap, nF) -T 10 .18 22 .4 15 0 S 100 1.8 30 .22 1000 18 50 .47 2200 30 80 1 100 2.2 150 4.7Schematic200 10 LINE LOAD 300 22 100 1000 2200 Note: Use any –Y (Y-cap) with any –X (Amps) rating e.g. RP425-300-2200-S 300 Amps with 2200nF y-caps Dimensions shown for reference only.RADIUS POWERwww.radiuspower.com Specifications subject to change. Standard & Custom Products PH 714-289-0055 FAX 714-289-214 |
|