Air Flow Controller
FKM 230.18 G S4
17.11.98 Details are subject to change without notice. WG 800
Proxitron GmbH - Gärtnerstr. 10 - D-25335 Elmshorn - Tel. 04121/2621-0 - Fax. 04121/24404 - mail@proxitron.de F22E
This air flow controller controls two independently
adjustable limit values upto a flow velocity of 30 m/s.
Short-circuit-proof normally open and normally close
outputs as well as two-colour LEDs indicate when the
values exceed or fall below the desired range. So troubles
such as flow failure, hose rupture and required exchange
of filter can be monitored in installations of inflow
technique.
Normally open (LED and potentiometer at the left, 20 pitches):
output connected through and given green light at min.
flow existing; red LED flow failure.
Normally close (LED and potentiometer at the right, 20 pitches):
output connected through and LED giving green light at
value fallen below the max. flow; red LED = flow too high.
Technical Data
Type FKM 230.18 GS4
Art.-Nr. 8041A
Output PNP n. o. + n. c.
Adjusting range normally open 1 - 30 m/s
Adjusting range normally close 8 - 30 m/s
Measuring principle calorimetric
Response time < 10 s
Readiness delay
after applying the supply voltage both
outputs are connected
30 s
during this time both
LEDs give green
intermittent light.
Supply voltage 24 V DC +10 / -15%
Ripple voltage max. 15%
Load current max. 0 - 400 mA
Short-time load current 4 A / 100 ms
Short circuit protection yes, pulsing
No-load current 50 mA
Voltage drop 1,5 V
Switching hysteresis 0,5 - 2 m/s
Ambient temperature -10 ... +60 °C
Protection class IP 65
Connection plug Lumberg M12
Function display 2 LEDs 2-colour
Housing material sensor part
electronic part with flange
plastic
aluminium
Weight 200 g
The air flow controller is mounted in such a way that the air can
flow onto the plane measuring surface (diameter 20 mm) from
random direction. For effective temperature compensation the
cylindrical part must be exposed to the same ambient
temperatures 30 mm upto the measuring surface. Quick
changes of temperature can result in misswitchings for a short
time.