Clean, Quiet, Reliable Backup Power.
Features and Benefits
Fuel Cell Technology - A new option in extended runtime backup power to replace or enhance battery or engine generator Systems.
Electrical Energy Storage Module (EESM) - Provides transient bridging power to ensure immediate response to power interruptions.
Fuel Storage System - Available in a variety of forms, hydrogen fuel storage is scalable to meet specific site and provider needs.
Thermal Management System - Extreme temperature tolerant design allows for operation from -40°C to +50°C.
Remote Monitoring/Control - Ensures system availability.
Reliable Product, Reliable Company - Offers standard two-year product warranty, extensive network of installation & service partners, product training, and service hotline.
Graphical Service Interface (SI) software allows local or remote monitoring & control of GenCore system.
GenCore cabinet with access door removed, showing the fuel cell stack.
Product Enhancements - GenCore options/upgrades are available on special request, please contact factory:
• Ultracapacitor-based EESM for high-temperature applications which can limit battery life
• Wireless communications for remote monitoring/control
• Extended runtime Hydrogen Storage Module (HSM) for backup applications of 72 hours or longer
• Reduced footprint HSM for applications at space-restricted sites
PRODUCT CHARACTERISTICS
5T48
5T24
GenCore.
Output
Maximum Output Power
5kW
Output Voltage Range, User Adjustable
-48.0 to-55.5 Vdc 1 +24.9 to+27.5 Vdc
Output Current Limit
115AmpsDC 240 AmpsDC
Maximum Output Ripple
250mV Pkto Pk, 100mV RMS
Typical Runtime with Std 6 Cylinder Hydrogen Storage Module (HSM)
27 Hours @ 2kW Output Power 11 Hours @ 5kW Output Power
Input
Gaseous Hydrogen
99.95% Purity, Dry, CGA G-5.3 Industrial Grade B
Supply Pressure
64 to 110 psig (4.4 to 7.6 bar)
Fuel Consumption
1.2 scfm (34 slm) or ~3 hrs/cylinder at 3kW output power
2.2 scfm (63 slm) or ~2 hrs/cylinder at 5kW output power
Environmental
Ambient Temperature
-40oFto+122oF(-40oCto+50oC) Full Rated Output Power at up to +25C
Output Power Derated to 4.92kW @ +35oC, 4.85kW @ +45oC & 4.55kW @ +50oC
Relative Humidity
5% to 95% non-condensing
Altitude
-197 ft to 13,150 ft (-60m to 4000m)
>1500 ft (457m) Output Power is Derated 75W per 1000 ft (305m)
Physical
Maximum Envelope Dimensions, not including fuel storage
46 inches Height x 36 inches Width x 32 inches Depth (117cm H x 91cm Wx 81cm D)
Weight
608 lbs (276 kg)
Safety
Compliance
FCC Class A, CSA (ANSI FC-1), CE and NEBS Level 3
Emissions
Water
Nominal: 0.53 gph (2.0 lph) Max: 1.1 gph (4.2 lph)
CO, CO2,SOx,NOx
Negligible
Audible Noise
< 60 dBA @1m
Sensors
Gas Hazard Detection
Included
Pad Shear, Water Intrusion, Tampering
Optional
Control
Microprocessor
Included
& Monitoring
Programmable Start Voltage Range
-48.0V to -55.0Vdc +24.9V to +27.0Vdc
Programmable Start Delay
50 seconds maximum
Communications
RS-232C & USB Included, Modem & Ethernet/IP Optional
Software
Graphical Service Interface provides status, event log & control
of unit via laptop PC (not included)
Alarms
4 Form C Dry Contacts
"Low Fuel", "Minor Alarm", "Major Alarm" & "Fuel Cell Running" all Included
PLUG POWER INC.
HEADQUARTERS 968 Albany Shaker Road Latham, New York 12110 Phone: 1.518.782.7700 Fax: 1.518.690.4445
EUROPE, MIDDLE EAST, AND AFRICA Wilmersdorf 50 7327 AC Apeldoorn The Netherlands
Phone: 31 55 53 81 000 Fax: 31 55 53 81 099
www. plugpower. com
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
06-003-2 09/07 3 PRINTED ON RECYCLED PAPER

pageCatalog pdf di En 2012-05-22-31