Soft Starters SAS 3 ... 11, SAS 11PUST, SAS 22PUST 1.01

Features:

A single-phase controlled soft starter A all devices for pole-changing motors A dual-voltage, for 400V and 230V networks A terminal arrangement suitable for switchgear connection

PETER_electronic_Katalog_E - 17119 1

A for snap-mounting on 35mm standard rail A integrated bypass relay A no mains neutral conductor (N) required A special voltages up to 640V

Soft Starters SAS 3 ... 11 SAS 11PUST, 22PUST

A also for single-phase applications A degree of protection IP 20 (SAS 3 ... SAS 11) degree of protection IP 00 (SAS 11PUST, 22PUST)

Function:

A soft start

Typical Applications:

A 2 separately adjustable parameters starting torque, starting time packaging machinery sliding doors belt drives conveying machinery door drives of passenger and goods lifts limitation of starting current for transformers A control contact for pole-changing motors

Upon Request:

1L1 3L2 5L3Trigger pulsegenerator X1 X2 A potential-free input control voltage 10 ... 30VDC A SAS 3 up to SAS 11: standard up to 480V special voltages 500V up to 640V (all types in 100mm-housing)
t Voltageselection A SAS 11PUST and SAS 22PUST: special voltages up to 690V
Ramp-functiongenerator Controlforbypass control contactfor pole-changingMotors M 2T1 4T2 6T3 X3 X4 Technical Data SAS 3 5,5 7,5 11 11PUST 22PUST Mains / Motor voltage X1-X2 jumpered according to DIN EN 50160 (IEC 38) 160 ... 240V 10% 400V 15% Mains / Motor voltage X1-X2 not jumpered according to DIN EN 50160 (IEC 38) 380 ... 480V 10% Device nominal current 6,5A 12A 16A 25A 25A 45A Mains frequency 50/60Hz Motor rating at 230V 1,5kW 3kW 4kW 5,5kW Motor rating at 400V 3kW 5,5kW 7,5kW 11kW 11kW 22kW min. motor current 10% of the device rated current Starting torque 0 ... 50% Starting time 0,5 ... 5s Reset time 200ms max. Switching cycle at 3x Ie and 5s t
an 240/h 200/h 120/h 70/h 240/h 120/h max. Cross-sectional area 2,5mm² 16mm² I²t-Value Power semiconductor 265A²s 610A²s 800A²s 1250A²s 5000A²s 10500A²s Ambient / Storage temperature 0°C ... 45°C / -25°C ... 75°C Weight / kg 0,3 0,3 0,5 0,5 2,7 3,0 Order number 20700. 40003 20700. 40005 20700. 40007 20700. 40011 20800. 38011 20800. 38022 Please observe supplementary sheet with dimensioning rules.