The directive 94/9/EU (ATEX 95) differs from previous documentation in its approach to capacitance and thus in the resulting permissible professional cable lengths in the hazardous area. In consideration of our customers, we have taken stock of this change and in the course of the new product approvals it will be seen that the maximum no-load voltages of several devices have been slightly reduced.
Therefore, when the need arises, existing plants can be equipped with ATEX-approved devices without impermissible cable lengths resulting from the peculiarities of the plant when the intrinsic safety is demonstrated.The device data sheets are identified accordingly.
Transmitter supply isolator
KFD2-CR-Ex1.30200
Transformerisolated amplifiersLogic controlunitsSolenoid driversRelay modules J? 1-channel
3-1+3-1+ U
Hazardous area = 26 V
Input EEx ia IIC; U
= 26 V 24 V DC 24 V DC supply voltage Output: allowable load max. 1 k Ω EMC acc. to NAMUR NE 21The KFD2-CR-Ex1.30200 supplies a 2-wire transmitter in the hazardous area with power. 2-wire
professional transmitters function exclusively with a 4mA...20mA signal. At least 17.6V is available for the transmitters at a measurement current of 20mA.
The input circuit's current is transferred to the safe area. The maximum load
KFD2-CR-Ex1.30200 KFD2-CR-Ex1.30200
Function
Successor KFD2-STC4-Ex1Connection
Safe area 7-9-8++-
+-
11+12- Power Rail
Input EEx ia IIC2-wire transmitter
OutputPower supply
Mechanical specifications Protection degree IP20 Mass approx. 150 gDimensions 20 x 118 x 115 mm (0.8 x 4.6 x 4.5 in) Data for application in conjunction with hazardous areas >
PTB 00 ATEX 2035
ConvertersTrip amplifiersIsolated repeatersRepeater, professional converter loop powered EC-Type Examination Certificate PTB 00 ATEX 2035, for additional certificates see www.pepperl-fuchs.com Group, category, type of protection ¬ II (1) G D [EEx ia] IIC [circuit(s) in zone 0/1/2]Input EEx ia IIC VoltageU >
10.5 VCurrentI >
13 mA PowerP >
34 mW (linear characteristic)Supply Safety maximum voltage U >
m 40 V DC (Attention! The rated voltage can be lower.)Output Safety maximum voltage U >
m 40 V DC (Attention! The rated voltage can be lower.)Statement of conformity TÜV 99 ATEX 1499 X, observe statement of conformity Group, category, type of protection, temperature classification ¬ II 3 G EEx nAC IIC T4 [device in zone 2]Electrical isolation Input/output safe electrical isolation acc. to EN 50020, voltage peak value 375 VInput/
power supply specification safe electrical isolation acc. to EN 50020, voltage peak value 375 V Directive conformity Directive 94/9 EC EN 50014, EN 50020, EN 50021 Entity parameter Certification number J.I.3002773 FM control drawing No. 116-0035Suitable for installation in division 2 yes
Connection lugs 1, 3; 2, 3; 4, 6; 5, 6 >
Date of issue10/24/05 – Catalogue K-system Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group Tel.: Germany +49 621 776-0 USA +1 330 4253555 Singapore +65 67799091 Internet http://www.pepperl-fuchs.com
97
Date of issue03/03/06 – Catalogue K-system Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
7