VBG-CCL-G4FAS-Interface professional gateway Technical data Function
General specifications
The VBG-CCL-G4F is a complete CC-Linkmaster for use in the field (IP65). The gate-way's G4 field housing has the same advan-
tages as the serial master in this design.Two buttons are used for address assign-ment of the AS-Interface slaves and accept-ance of the desired configuration. Inconfiguration mode, all detected AS-Interfaceslaves are displayed on the 2-digit LCD. Innormal operation, the LCD is blank unlessthe master detects a faulty AS-Interfaceslave. The LEDs, located on the front panel,
show the current status of the AS-i line.
AS-Interface specification V2.11 >
Indicators/operating means
LC display, two-digit address display, error messageLED SD CC Link send data; LED green >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl cabinetI/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories LED RD CC Link receive data; LED greenLED AS-i ACTIVE AS-Interface operation normal; LED green LED CONFIG ERR configuration error; LED redLED PWR voltage ON; LED green LED L RUN CC link in operation; LED greenLED L ERR CC Link error; LED red >
LED PRG ENABLE autom. programming; LED greenLED PRG MODE projecting mode active; LED yellow >
The VBG-CCL-G4F provides 16kBytes ofprogram memory, 8kBytes of main memory,1024 counters and 1024 timers for PLC func-tionality. These capacities suffice to processthe data on the AS-Interface. Thus the mas-ter can also be operated in "stand-alone"mode. The program processing time is 2msper 1000 word commands. The programminglanguage is based on the STEP5
LED U AS-i AS-Interface voltage; LED greenSwitch SET Selection and setting of a slave address Button MODE Mode selection/save configuration >
Electrical specifications
Insulation voltage U >
i 500 VRated operational voltage U >
e from AS-Interface Rated operational current I >
e 200 mA from AS-Interface >
Interface
Protocol according to CC-Link specificationInterface type remote device, 3 occupied stations Transfer rate 156 kBit/s up to 10 MBit/s >
program-ming language. The AS-Interface CTRLfunctions (upload, download, start, stop, reador write internal memory) are available in
expanded mode.
Connection
AS-Interface cable piercing techniqueCC Link
Suppliers of cable gland M16x1.5 and cage
professional spring terminals >
Ambient conditions
Ambient temperature 0 ... 55 °C (273 ... 328 K) Storage temperature -25 ... 85 °C (248 ... 358 K) >
Accessories
Mechanical specifications
Protection degree IP65 according to EN 60529Mass 355 g >
U-G1P Base for connection to round cable (EMS;AS-Interface only) VAZ-G4-B
Blind plug PG7
No additional software is required.
Note
U-G1F base is included with delivery
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m