VBG-PB-G4F-R4AS-Interface professional gateway Technical data Function
General specifications
The VBG-PB-G4F-R4 is a complete PROFI-BUS slave with an IP67 rating designed foruse in the field. The G4 field housing of the
Profibus gateway offers all the advan-tages of the serial master in this design.The VBG-PB-G4F-R4 is a modular PROFI-BUS slave. This means that the user can usethe PROFIBUS configuration tool to specifywhat data will be transferred via the PROFI-BUS. This makes it possible to adjust theamount of data to be transferred via PROFI-BUS.
In addition, this gateway supports acyclicalcommunication of the PROFIBUSDPV1.These acyclical services can be used toaccess a mailbox in the gateway that provideaccess to all the data that are made availableby the AS-Interface/PROFIBUS Gateway.Two push buttons are used for addressassignment, acceptance of the desired con-figuration and for adjustment of the PROFI-
BUS address and baud rate. In configurationmode, all detected AS-Interface slaves aredisplayed on the 2-digit LCD. In normal oper-
ation, the LCD is blank unless the masterdetects a faulty AS-Interface slave. There are7LEDs on the front panel, showing the cur-rent status of the AS-Interface line.
AS-Interface specification V2.11 >
Indicators/operating means
Led display, two-digit address display, error messageLED BUS ACTIVE PROFIBUS master detected; LED green >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl cabinetI/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories LED AS-i ACTIVE AS-Interface operation normal; LED greenLED CONFIG ERR configuration error; LED red LED PRG ENABLE autom. programming; LED greenLED ENERGY voltage ON; LED green LED PRJ MODE projecting mode active; LED yellowLED U AS-i AS-Interface voltage; LED green Switch SET Selection and setting of a slave addressButton MODE Mode selection/save configuration >
Electrical specifications
Insulation voltage U >
i 500 V Rated operational voltage U >
e from AS-InterfaceRated operational current I >
e 180 mA from AS-Interface >
Interface
Protocol PROFIBUS Interface type RS 485Transfer rate 9.6 kBit/s ... 12 MBit/s self-synchronising >
Connection
PROFIBUS
Suppliers of cable gland M16x1.5 and cage
professional spring terminals AS-Interface cable piercing technique >
Ambient conditions
Ambient temperature 0 ... 55 °C (273 ... 328 K)Storage temperature -25 ... 85 °C (248 ... 358 K) >
Mechanical specifications
Protection degree IP65 according to EN 60529 Mass approx. 355 g >
VAZ-SW-ACT32 Full version of the AS-i Control Tools
The device is supplied with the configuration data files (GSD) as well as a restricted version ofthe AS-i Control Tools software. The software performs the addressing, programming andmonitoring of the AS-Interface network. The full version of the AS-i Control Tool is availableas an accessory and features an expanded diagnostics professional monitor as well as a larger programmemory for AS-Interface Control which makes it possible to detect faulty telegrams of slaves.A GSD file can be easily created for the PROFIBUSDP using the GSD assistant, wherebythe size of the I/O windows can be conveniently adapted to the AS-Interface circuit's load andthe AS-Interface configuration can be stored within the GSD file. A text file is also created,which documents the status of AS-Interface data in the gateway's I/O window.
VAZ-PB-SIM PROFIBUS master professional simulator VAZ-G4-R4 Interface cable for direct connection of the master to a PC U-G1P Base for connection to round cable (EMS;AS-Interface only)
Note: The VAZ-PB-SIM accessory is required for the AS-i Control Tool.
Note
U-G1F base is included with delivery
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m
39