| | Technical data | |
| | General specifications | | |
| | Slave type | Standard slave | |
| | Indicators/operating means | | |
| | LED FAULT | communication error / address is 0; LED red | |
| | LED PWR | AS-Interface voltage; LED green | |
| | Electrical specifications | | |
| | Auxiliary voltage (output) UAUX | 24 V DC ± 15 % PELV (protection class 3 according to VDE 0106/IEC 364-4-41) | |
| | Rated operational voltage Ue | 26.5 ... 31.6 V from AS-Interface | |
| | Rated operational current Ie | < 20 mA | |
| | Input | | |
| | Number/Type | 1 Input for 2-wire sensor | |
| | Supply | from external auxiliary voltage UAUX | |
| | Switching point | OFF < 0.8 mA ON > 5 mA | |
| | Output | | |
| | Number/Type | 3 electronic outputs, PNP | |
| | Supply | from external auxiliary voltage UAUX | |
| | Current | 20 mA per output | |
| | Programming instructions | | |
| | Profile | S-9.F | |
| | IO code | 9 | |
| | ID code | F | |
| | ID2 code | 0 | |
| | Data bits (function via AS-Interface) | input output | |
| | DO | IN4 O4 | |
| | D1 | - OUT2 | |
| | D2 | -OUT3 | |
| | D3 | IN1 - | |
| | Parameter bits (programmable via AS-i) | function | |
| | PO | not used | |
| | P1 | not used | |
| | P2 | not used | |
| | P3 | not used | |
| | Ambient conditions | | |
| | Ambient temperature | 0 ... 70 °C (273 ... 343 K) | |
| | Storage temperature | -40 ... 70 °C (233 ... 343 K) | |
| | Mechanical specifications | | |
| | Protection degree | IP67 according to EN 60529 The protection class appplies only for installation of the module in a connection housing for parts of the module located outside of the connection housing (external M12 connection, inside cable connection). | |
| | Connection | AS-Interface and auxiliary voltage: M12x1 round connector manufacturers auxiliary voltage, input and outputs: 20 cm connection cable | |
| | Mass | 110 g | |
| | | | |