VAA-LT2-G1AS-Interface pushbutton module Technical data Function
General specifications
The illuminated pushbutton module VAA-LT2-G1 provides a link between the operat-ing personnel and the AS-Interface master.
The current status can be displayed bymeans of the LEDs integrated in the push-buttons.The illuminated pushbutton has IP67 protec-tion and is therefore suitable particularly foruse in the field.Various bases are available for the module.Use the U-G1F base to connect to the AS-Interface flat wiring, and use the U-G1P base
to connect to the round cable.The output modules often have to bemounted in series with the illuminated push-button. The outputs of the output modulesare supplied externally with power. If thepower is supplied via a flat cable, the powersupply lead has to be mounted in the base ofthe input module. The U-G1FF base shouldbe used in this case. The VAA-LT2-G1 then
uses the AS-Interface cable rather than thepower cable.
Slave type Standard slave >
Indicators/operating means
Button 2 integrated,protected against accidental activation,keys can be individually labelled,
professional labeling field on the module >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl cabinetI/O ModulesField applicationAnalogue modules Electrical specifications
Protection class IIIRated operational voltage U >
e 26.5 ... 31.6 V from AS-Interface Rated operational current I >
e 55 mA (LEDs on) >
Programming instructions
Profile S-3.FIO code 3 ID code F Data bits (function via AS-Interface) inputoutput D0 Button 2 red-D1 Button 1 green- D2 -LED 2 redD3 -LED 1 green Parameter bits (programmable via AS-i) P0 not used P1 not usedP2 not used P3 not used >
Ambient conditions
Accessories
Ambient temperature -25 ... 60 °C (248 ... 333 K)Storage temperature -40 ... 85 °C (233 ... 358 K) >
VBP-HH1
Mechanical specifications
Hand-held programming device
Protection degree IP67 according to EN 60529 Connection cable piercing method or terminal compartmentflat cable or standard round cable >
Matching system components
U-G1F Base for connection to flat cable (EMS; AS-Interface only) U-G1FA Base with addressing jack for connection to flat cable (EMS; AS-Interface only) U-G1P Base for connection to round cable (EMS;AS-Interface only)
Other modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m
223