VAA-4E2A-G1-ZE/P-SAS-Interface pneumatic module Technical data Function
General specifications
The VAA-4E2A-G1-ZE/P-S module features4inputs for the connection of 2- or 3-wiresensors and 2pneumatic outputs with a high
air flow rate for direct control of pneumaticdrives in the field. 2separate 3/2-way valvesare integrated in the module. Both the valveand the sensors connected to the moduleare supplied via the bus cable.The sensors are connected to the module viaM12x1-circular connectors specifications; the outputs areconnected to the pneumatic drive via stand-ard professional hose plug-in connectors (LEGRIS LF
3000, 8mm).Various bases are available for the mod-ule.The U-G1F (or U-G1FA) base providesthe connection to the AS-Interface flat cabling;the U-G1P base provides the connection to around cable.It happens very frequently that output mod-ules must be installed in series with thepneumatic module. If the outputs of the out-
put modules are supplied with externalpower transferred via a flat cable, a suitableEEMS base (U-G1FF or U-G1FFA) must be
used for the pneumatic module. In this case,VAA-4E2A-G1-ZE/P-S accesses the AS-Interface cable instead of the power supplycable.
Slave type Standard slave >
Indicators/operating means
LED AS-i AS-Interface voltage; LED greenLED IN switching state (input); 4 LED yellow >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl cabinetI/O ModulesField applicationAnalogue modules LED OUT switching state (output); 2 LED yellow >
Electrical specifications
Rated operational voltage U >
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I >
e 45 mA (without sensors) 200 mA (complete) >
Input
Number/Type 2x 2 inputs for 2- or 3-wire sensors (PNP), DC Supply from AS-InterfaceCurrent loading capacity 100 mA, short-circuit proof Switching point OFF: 1.5 mAON: 5 mA, 10 V >
Output
Number/Type 2 pneumatic outputs with separated 3/2-way
cocks >
Pneumatic output
Venting guide Sinter filterCompressed air 2 ... 8 bar, filtered (5 m), oiled or unoiled
pneumatics Air throughput 550 Nl/min at 6/0 bar350 Nl/min at 6/5 barValve cross-section 5 mm >
Note: The slave address must be programmed
before commissioning (default setting 0).Medium: Filtered (5µm), oiled or unoiledcompressed air (2...8bars).
Programming instructions
Profile S-7.F >
Warning:
IO code 7ID code F >
Dangerous electric voltage can lead to elec-tric shock and burns. The system must bedisconnected from the power supply specifications beforethe beginning of the works.
ID1 code FID2 code F Data bits (function via AS-Interface) inputoutput D0 IN1- D1 IN2-D2 IN3OUT3 D3 IN4OUT4 Parameter bits (programmable via AS-i) P0 not usedP1 not used P2 not usedP3 not used >
Ambient conditions
Ambient temperature 0 ... 55 °C (273 ... 328 K) Storage temperature -20 ... 85 °C (253 ... 358 K) >
Accessories
Mechanical specifications
VBP-HH1
Protection degree IP65 according to EN 60529Connection cable piercing method or terminal compartmentflat cable or standard round cableinputs: M12 x 1 round connectoroutputs: plug-in hose connector (8 mm) >
Hand-held programming device
Other modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Matching system components
U-G1F Base for connection to flat cable (EMS; AS-Interface only)
Mass approx. 200 gMounting DIN rail or screw mounting >
U-G1P Base for connection to round cable (EMS;AS-Interface only) U-G1FA Base with addressing professional jack for connection to flat cable (EMS; AS-Interface only)
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m
219