VBA-2E-KE2-I/UAS-Interface analogue module Technical data Function
Indicators/operating means
The VBA-2E-KE2-I/U analog module isequipped with two analog inputs that can becurrent inputs (4mA...20mA) or voltage
inputs (0...10V). The module can also beconnected as a combined current/voltagemodule. In this case the module type mustbe the same for each channel.Depending on the setting of the internal slid-ing switch, the supplier of power supply for the measure-ment value industrial transmitter is via the module(from the AS-Interface) or through an exter-nal power supply. The input power supply
selection is displayed via the INT and AUXLEDs.Measurement values are converted and datais transferred asynchronously based on AS-Interface Profile7.3. The resolution of analogvalues is 16bits with a value range of4,000...20,000 (current module) or0...10,000 (voltage module). Power faultscan be eliminated with a parameterizable fil-
ter (50Hz/60Hz) in the A/D professional converter.The secondchannel can be turned off with asecond industrial slide switch to allow for faster data
transfer.The housing, only 22.5mm in width, takes uplittle place in the switch professional cabinet. The moduleis installed by snapping on the 35-mm carrierrail in accordance with EN50022.It can be connected by plug-in terminals(COMBICON). 4X terminal blocks (black) areused for the inputs. The connection of theexternal auxiliary supply and AS-Interface ismade through the 2-way-terminal blocks(auxiliary supply gray, AS-Interface yellow).This makes it possible to separate individualsensors or to supply power during commis-sioning or servicing.
LED FAULT error display; LED redred: communication errorred flashing: periphery faultLED INT Internal input voltage active; LED green >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl cabinetI/O ModulesField application LED PWR AS-Interface voltage; LED greenLED AUX ext. auxiliary voltage U >
AUX ; LED green LED -/OK Status input signal; LED greenOff: Not connected (Only current module)On: Signal within measuring rangeFlashing: Signal outside measuring rangeLED U/I Current or voltage module; Green LEDOff: Voltage inputOn: Current input >
Electrical specifications
Auxiliary voltage (output) U >
AUX 24 V DC ± 15 % PELV(protection class 3 according to VDE 0106/IEC 364-4-41) Insulation voltage U >
i 500 VRated operational voltage U >
e 26.5 ... 31.6 V from AS-Interface Rated operational current I >
e 80 mA >
Input
Number/Type 2 analogue inputsCurrent: 4 ... 20 mAvoltage: 0 ... 10 VSupply from AS-Interface or from external auxiliary voltage as required U >
AUX Current loading capacity 40 mA per inputInput resistance For current module: 50 For voltage module: 100 k Switching point Changeover current/voltage module:current module with I >
input 1 mAvoltage module with U >
input 1 VResolution 16 Bit / 1 A (Current module) or16 bit / 1 mV (Voltage module) >
Programming instructions
Note:
Profile S-7.3.D >
The device is equipped with communicationmonitoring that turns off the outputs if no AS-Interface communication has taken place
with the device for more than 40ms.An overload of the internal input supply isreported by the 'periphery error' to the AS-
Interface master. Communication over theAS-Interface remains in effect.
IO code 7ID code 3 ID2 code D Data bits (function via AS-Interface) The transfer of the data value is based on AS-Interface Profile 7.3. Parameter bits (programmable via AS-i) functionP0 mains power frequency filterP0=1, 50 Hz
industrial filter activeP0=0, 60 Hz filter active >
Analogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories P1 projecting of the 2nd channelP1=1, channel 2 is projectedP1=0, channel 2 is not projectedP2 Message of peripheral errorP2=1, periphery fault is reportedP2=0, periphery fault is not reported P3 not used >
Standard conformity
Electromagnetic compatibility EN50295, EN61326 >
Ambient conditions
Accessories
Ambient temperature 0 ... 70 °C (273 ... 343 K)Storage temperature -25 ... 85 °C (248 ... 358 K) >
VBP-HH1 Hand-held programming device
Mechanical specifications
Protection degree IP20 according to DIN 40050 >
VAZ-PK-1,5M-V1-G
Connection removable terminals, terminal connection 2.5 mm >
2 Connection cable module/hand-held pro-
gramming device
Mass 350 g Mounting DIN rail >
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m
205