VBA-2A-G4-UAS-Interface analogue module Technical data Function
Indicators/operating means
The VBA-2A-G4-U analogue module has twovoltage outputs 0V...10V. The asynchro-nous transformation of measured values and
the data transfer is accomplished in accord-ance with AS-Interface profile7.3. Themeasured-value professional transmitter can be suppliedfrom the AS-Interface or from the externalauxiliary power via the black flat cable,depending on the wiring of the industrial plug-in jump-ers. The resolution of the analogue values is13bit.The IP65 rated G4 module is especially suit-
able for rough conditions. Connection to theoutputs is established by means of cableglands and cage tension professional spring terminalsthus making the installation especially user-friendly. For pre-addressing the module it canbe plugged directly onto the adapter of thehand-held programming device VBP-HH1.Both flat and round professional cables can be used forthe connection of the AS-Interface transmis-
sion line and the external 24VDC powersupply. Use the U-G1FF base for the AS-Interface flat cable. The AS-Interface stand-
ardised EEMS interface, uses the cablepiercing method to connect both the yellowand black flat cables.Use the U-G1PP base for a round cable. TheAS-Interface cable as well as the externalpower supply may be connected within theU-G1PP base.
LED FAULT error display; LED redred: communication errorred flashing: periphery faultLED PWR AS-Interface voltage; LED green >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl cabinetI/O ModulesField application LED ANALOG status output signal; LED greenoff: not connected (periphery fault)green: 0 V U 11.5 Vgreen flashing: U > 11.5 V (periphery fault)LED AUX ext. auxiliary voltage U >
AUX ; LED green >
Electrical specifications
Auxiliary voltage (output) U >
AUX 24 V DC ± 15 % PELV Protection class IIIRated operational voltage U >
e 26.5 ... 31.6 V from AS-Interface Rated operational current I >
e 80 mA >
Output
Number/Type 2 analogue outputs (voltage), 0 ... 10 VSupply from AS-Interface or from external auxiliary voltage as required U >
AUX Resolution 13 Bit / 1 mV >
Programming instructions
Profile S-7.3.5IO code 7 ID code 3ID2 code 5 Data bits (function via AS-Interface) The transfer of the data value is based on AS-Interface Profile 7.3. Parameter bits (programmable via AS-i) function P0 not usedP1 projecting of the 2nd channelP1=1, channel 2 is projectedP1=0, channel 2 is not projected P2 Message of peripheral error
P2=1, periphery fault is reported
P2=0, periphery fault is not reportedP3 not used >
Accessories
Ambient conditions
VBP-HH1
Ambient temperature 0 ... 70 °C (273 ... 343 K) >
Hand-held programming device
Storage temperature -25 ... 85 °C (248 ... 358 K) >
Mechanical specifications
VAZ-G4-B
Protection degree IP65 according to EN 60529Connection cable piercing method or terminal compartmentflat cable yellow/flat cable black or standard round cableinputs/outputs: 2xscrewed connection M16x1.5 and cage
suppliers of clamp terminals, 1xscrewed connection M12x1.5 (not used) >
Blind plug PG7
Analogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Matching system components
U-G1FF
Mass 350 gMounting DIN rail >
Base for connection to flat cable (EEMS; AS-Interface and external auxiliary pow-er) U-G1FFA Base with addressing professional jack for connection to flat cable (EEMS; AS-Interface and ex-ternal auxiliary power) U-G1PP Base for connection to round cable (EEMS;
AS-Interface and external auxiliary volt-age)
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m
203