VBA-2A-G4-IAS-Interface analogue module Technical data Function
Indicators/operating means
The VBA-2A-G4-I analogue module has twoanalogue current outputs 0mA...20mA.Measured value conversion and data trans-
mission are performed asynchronously inaccordance with AS-Interface profile7.3.Depending on how the plug-in jumpers arewired, the outputs can be powered from theAS-Interface or the external auxiliary powerthrough the black flat wire. The resolution ofanalog values is 13bits.The G4 module in IP65 is particularly suita-ble for hard field use. The connection to the
outputs is established by screwed connec-tions and cage-suppliers of clamp terminals. This makesthe installation especially user friendly. Themodule can be plugged directly onto theadapter of the VBP-HH1 of the hand heldprogramming device for pre-addressing.The connection to the AS-Interface transmis-sion line and the external 24VDC powersupply can be made with flat wire or round
cable. If AS-Interface flat wire is used, thelower part of the U-G1FF should be used.The contact to the two lines is made with the
EEMS interface standardised for AS-Inter-face, i.e. using the insulation penetrationtechnique.For a round cable, the U-G1PP base shouldbe used. Here as well, it is possible to con-nect both the AS-Interface lead and theexternal professional power supply in the base.
LED FAULT error display; LED redred: communication errorred flashing: periphery faultLED PWR AS-Interface voltage; LED green >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl cabinetI/O ModulesField application LED ANALOG status output signal; LED greenoff: not connected (periphery fault)green: 0 mA I 23 mAgreen flashing: I > 23 mA (periphery fault)LED AUX ext. auxiliary voltage U >
AUX ; LED green >
Electrical specifications
Auxiliary voltage (output) U >
AUX 24 V DC ± 15 % PELV Protection class IIIRated operational voltage U >
e 26.5 ... 31.6 V from AS-Interface Rated operational current I >
e 80 mA >
Output
Number/Type 2 analogue outputs (current), 0 ... 20 mASupply from AS-Interface or from external auxiliary voltage as required U >
AUX Resolution 13 Bit / 1 A >
Programming instructions
Profile S-7.3.5IO code 7 ID code 3ID2 code 5 Data bits (function via AS-Interface) The transfer of the data value is based on AS-Interface Profile 7.3. Parameter bits (programmable via AS-i) function P0 not usedP1 projecting of the 2nd channelP1=1, channel 2 is projectedP1=0, channel 2 is not projected P2 Message of peripheral error
P2=1, periphery fault is reported
P2=0, periphery fault is not reportedP3 not used >
Accessories
Ambient conditions
VBP-HH1
Ambient temperature 0 ... 70 °C (273 ... 343 K) >
Hand-held programming device
Storage temperature -25 ... 85 °C (248 ... 358 K) >
Mechanical specifications
VAZ-G4-B
Protection degree IP65 according to EN 60529Connection cable piercing method or terminal compartmentflat cable yellow/
flat wire black or standard round cableinputs/outputs: 2xscrewed connection M16x1.5 and cage clamp terminals, 1xscrewed connection M12x1.5 (not used) >
Blind plug PG7
Analogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Matching system components
U-G1FF
Mass 350 gMounting DIN rail >
Base for connection to flat cable (EEMS; AS-Interface and external auxiliary pow-er) U-G1FFA Base with addressing professional jack for connection to flat cable (EEMS; AS-Interface and ex-ternal auxiliary power) U-G1PP Base for connection to round cable (EEMS;
AS-Interface and external auxiliary volt-age)