VAA-4E-G4-NAS-Interface sensor module Technical data Function
General specifications
The VAA-4E-G4-N is an AS-Interface cou-pling module with 4inputs for sensors perDIN19234 (NAMUR), which can be moni-
tored for lead breakage and short circuit (seenote).The IP67 rated G4 module is especially suit-able for rough conditions. Sensors attach tocable glands and cage tension professional spring termi-nals. For pre-addressing the module it canbe plugged directly onto the adapter of thehand-held programming device VBP-HH1.Both flat and round professional cables can be used for
the connection of the AS-Interface transmis-sion line. Use the U-G1F or U-G1FF base forAS-Interface flat ropes. The connection tothe AS-Interface cable is established via thestandardised EMS interface (cable piercingmethod). The U-G1F base can also be usedas IP67 AS-Interface distribution rack. Usethe U-G1FF base, when modules with out-puts are mounted in series with the module.
The flat cable for external suppliers of power supply canbe placed in this base, since the moduledoes not access the supply line.
Use the U-G1P or U-G1PP base for roundcables. These bases have the same func-tionality as the U-G1F or the U-G1FF bases.
Slave type Standard slave >
Indicators/operating means
LED PWR AS-Interface voltage; LED greenLED IN 4 dual LED yellow/redyellow: switching state (input)red: lead breakagered and yellow: line short-circuit >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl professional cabinet Electrical specifications
Protection class III Rated operational voltage U >
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I >
e 40 mA >
Input
Number/Type 4 Inputs for NAMUR sensors Supply from AS-InterfaceVoltage 8 V Switching point OUT 1.8 mAON 1.5 mALead monitoring lead breakage: 0.15 mA lead short-circuit: 6 mA >
Programming instructions
Profile S-0.F >
Note:
IO code 0ID code F >
Lead breakage/short circuit monitoring isactivated or deactivated per channel, by
means of the parameter bits P0...P3. Allerror conditions are linked by an OR-logic-operation. In a failure case, the AS-Interfacemaster indicates an error and the moduledisconnects from the AS-Interface, while thewatchdog is activated.
Data bits (function via AS-Interface) inputoutput D0 IN1- D1 IN2-D2 IN3- D3 IN4- Parameter bits (programmable via AS-i) function P0 lead monitoring IN1P0 = 1 (basic setting), monitoring deactivated
P0 = 0, monitoring activatedP1 lead monitoring IN2P1 = 1 (basic setting), monitoring deactivatedP1 = 0, monitoring activated >
I/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories P2 lead monitoring IN3P2 = 1 (basic setting), monitoring deactivatedP2 = 0, monitoring activatedP3 lead monitoring IN4P3 = 1 (basic setting), monitoring deactivated
P3 = 0, monitoring activated >
Accessories
Ambient conditions
VBP-HH1
Ambient temperature -25 ... 60 °C (248 ... 333 K) >
Hand-held programming device
Storage temperature -25 ... 85 °C (248 ... 358 K) >
Mechanical specifications
VAZ-G4-B
Protection degree IP67 according to EN 60529Connection cable piercing method or terminal compartmentflat cable yellow or standard round cableinputs: screwed connection M12x1,5 and cage-clamp termi-nals >
Blind plug PG7
Matching system components
Mass 180 gMounting DIN rail or screw mounting >
U-G1F Base for connection to flat cable (EMS; AS-Interface only) U-G1FA Base with addressing professional jack for connection to flat cable (EMS; AS-Interface only) U-G1P Base for connection to round cable (EMS;AS-Interface only)
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com