VAA-4E-G4-ZAS-Interface sensor module Technical data Function
General specifications
The VAA-4E-G4-Z AS-Interface couplingmodule is a field module with 4inputs. Theinputs permit the connection of 2-wire sen-
sors, which can be monitored for lead break-age and short circuit (see note).The IP67 rated G4 module is especially suit-able for rough conditions. Sensors attach tocable glands and cage tension professional spring termi-nals. For pre-addressing the module it canbe plugged directly onto the adapter of thehand-held programming device VBP-HH1. Both flat and round professional cables can be used for
the connection of the AS-Interface cable.Usethe U-G1F or U-G1FF base for flat cables.The connection to the AS-Interface cable isestablished via the standardised EMS inter-face (cable piercing method). The U-G1Fbase can also be used as IP67 AS-Interfacedistribution box. Use the U-G1FF base, whenmodules with outputs are mounted in serieswith the module. The flat cable for external
switched mode power supply can be placed in this basesince the module does not access the supplyline. Use the U-G1P or the U-G1PP base for around cable. These bases have the samefunctionality as the U-G1F or the U-G1FFbases.
Slave type Standard slave >
Indicators/operating means
LED PWR AS-Interface voltage; LED greenLED IN 4 dual LED yellow/redyellow: switching state (input)red: lead breakagered and yellow: line short-circuit >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl professional cabinet Electrical specifications
Protection class III Rated operational voltage U >
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I >
e 40 mA >
Input
Number/Type 4 inputs for 2-wire sensors, DC Supply from AS-InterfaceVoltage 15 V Input current 8 mA (limited internally)Switching point 0 (unattenuated) 1.5 mA1 (attenuated) 4.5 mA Lead monitoring lead breakage: 0.5 mA lead short-circuit: 5 mA >
Programming instructions
Note:
Profile S-0.FIO code 0 >
Lead breakage/short circuit monitoring is
activated or deactivated per channel, bymeans of the parameter bits P0...P3. Allerror conditions are linked by an OR-logic-operation. In a failure case, the AS-Interfacemaster indicates an error and the moduledisconnects from the AS-Interface, while themonitoring function is activated.
ID code F Data bits (function via AS-Interface) inputoutput D0 IN1-D1 IN2- D2 IN3-D3 IN4- Parameter bits (programmable via AS-i) functionP0 lead monitoring IN1P0 = 1 (basic setting), monitoring deactivatedP0 = 0, monitoring activated >
I/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories P1 lead monitoring IN2
P1 = 1 (basic setting), monitoring deactivated
P1 = 0, monitoring activatedP2 lead monitoring IN3P2 = 1 (basic setting), monitoring deactivatedP2 = 0, monitoring activated P3 lead monitoring IN4P3 = 1 (basic setting), monitoring deactivatedP3 = 0, monitoring activated >
Accessories
VBP-HH1
Ambient conditions
Hand-held programming device
Ambient temperature -25 ... 60 °C (248 ... 333 K)Storage temperature -25 ... 85 °C (248 ... 358 K) >
VAZ-G4-B
Mechanical specifications
Blind plug PG7
Protection degree IP67 according to EN 60529 Connection cable piercing method or terminal compartmentflat cable yellow or standard round cableinputs: screwed connection M12x1,5 and cage-clamp termi-nalsMass 180 g >
Matching system components
U-G1F Base for connection to flat cable (EMS; AS-Interface only)
Mounting DIN rail or screw mounting >
U-G1FA Base with addressing professional jack for connection to flat cable (EMS; AS-Interface only) U-G1P Base for connection to round cable (EMS;
AS-Interface only)
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com