VBA-4E3A-G4-ZE/E2AS-Interface sensor-/actuator module Technical data Function
General specifications
The VBA-4E3A-G4-ZE/E2 is an AS-Interfacecoupling module with four inputs and threeoutputs. Mechanical contacts and 2- and 3-
wire sensors can be connected to the inputs.The sensors are supplied via the module.The outputs are electronic outputs, whichcan be loaded to 24VDC and 2A or 1.5Aper output (total load <4A).The G4 module is especially suitable forrough conditions. Sensors and actuatorsattach to manufacturers of cable glands and cage tensionspring terminals thus making the installation
especially user-friendly. For pre-addressingthe module it can be plugged directly ontothe adapter of the hand-held programmingdevice VBP-HH1.The current switching state of each channelis indicated by an LED, located on the mod-ule's top side. In the case of communicationerrors on the bus, the outputs are de-ener-gised via an integrated watchdog.
Both flat and round professional cables can be used forthe AS-Interface transmission line and theexternal 24VDC power supply manufacturers. Use the
U-G1FF base for the AS-Interface flat cable.The AS-Interface standardised EEMS inter-face, uses the cable piercing method to con-nect both the yellow and black flat wires.Use the U-G1PP base for the round cable.The AS-Interface-cable as well as the exter-nal power supply may be connected withinthis base.
Slave type A/B slave >
Indicators/operating means
LED PWR/FAULT dual LED green/redgreen: AS-Interface voltagered: communication error or address 0green/red flashing: overload sensor supplyLED AUX ext. auxiliary voltage U >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl professional cabinet AUX ; LED green LED IN switching state (input); 4 LED yellowLED OUT switching state (output); 3 LED yellow >
Electrical specifications
Auxiliary voltage (output) U >
AUX 24 V DC ± 15 % PELV Protection class IIIRated operational voltage U >
e 26.5 ... 31.6 V from AS-Interface Rated operational current I >
e 60 mA (without sensors) / max. 240 mA >
Input
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DCSupply from AS-Interface Voltage 21 ... 31 VCurrent loading capacity 180 mA (T >
B 40 °C), 140 mA (T >
B 60 °C), short-circuit proof Input current 8 mA (limited internally)Switching point according to DIN EN 61131-2 (Type 2) 0 (unattenuated) 2 mA1 (attenuated) 4 mA >
Output
Number/Type 3 electronic outputs, PNP >
Note:
Supply from external auxiliary voltage U >
The device incorporates communicationmonitoring, which switches off power to theoutputs if no communication has taken placeon the AS-Interface line for longer than40ms.An overloading of the internal input supply orof the outputs is signalled to the AS-Interfacemaster via the "Peripheral fault" function.Communication via the AS-Interface remains
intact.
AUX Current 4 A totalOUT 1, OUT 2: 2A per output
OUT 3: 1.5A Voltage (U >
AUX - 0,5 V) >
I/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Programming instructions
Profile S-7.A.0IO code 7 ID code AID1 code 7 ID2 code Data bits (function via AS-Interface) inputoutput D0 IN1OUT1D1 IN2OUT2 D2 IN3OUT3D3 IN4- Parameter bits (programmable via AS-i) functionP0 not used P1 not usedP2 not used >
Accessories
P3 not used >
Ambient conditions
VBP-HH1
Ambient temperature -25 ... 60 °C (248 ... 333 K)Storage temperature -25 ... 85 °C (248 ... 358 K) >
Hand-held programming device VAZ-G4-B
Mechanical specifications
Blind plug PG7
Protection degree IP65 according to EN 60529 Connection cable piercing method or terminal compartmentflat cable yellow/flat cable black or standard round cableinputs/outputs: screwed connection M12x1,5 and cage
workholding terminalsMass 350 g >
Matching system components
U-G1FF Base for connection to flat cable (EEMS; AS-Interface and external auxiliary pow-
er)
Mounting DIN rail or screw mounting >
U-G1FFA Base with addressing professional jack for connection to flat cable (EEMS; AS-Interface and ex-ternal auxiliary power) U-G1PP Base for connection to round cable (EEMS;
AS-Interface and external auxiliary volt-age)
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
171