VAA-4A-G2-E2AS-Interface actuator module Technical data Function
General specifications
The VAA-4A-G2-E2 is an AS-Interface cou-pling module with four electronic outputs,which can be loaded to 24VDC and 1.5A.
The IP67 flat module features an integratedaddressing professional jack and is ideal for applicationsin the field. Connection to the industrial actuators is provided viaM12x1 screw connections. The currentswitching state of each channel is indicatedby an LED, located on the module's top side.Similarly, an LED is provided to professional monitor theAS-Interface communication and to indicate
that the module has the address0. If an AS-Interface communication error occurs, theoutputs are de-energised.The voltages of the AS-Interface and of theexternal switched mode power supply are also indicated byan LED each. The U-G3FF mounting base is normally usedfor the connection of the AS-Interface flatcable and the external 24V DC power sup-
ply. The specially designed base enablesusers to connect flat cables from both sides.This means, for example, that 90° curves can
be laid with very tight radii (variable flat cableguide).
Slave type Standard slave >
Indicators/operating means
LED FAULT communication error / address is 0; LED redLED PWR AS-Interface voltage; LED green >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl professional cabinet LED AUX ext. auxiliary voltage U >
AUX ; LED greenLED OUT switching state (output); 4 LED yellow >
Electrical specifications
Auxiliary voltage (output) U >
AUX 24 V DC ± 15 % PELV Protection class IIIRated operational voltage U >
e 26.5 ... 31.6 V from AS-Interface Rated operational current I >
e 30 mA >
Output
Number/Type 4 electronic outputs, PNPSupply from external auxiliary voltage U >
AUX Current 1.5 A pro output, 4 A totalVoltage (U >
AUX - 0,5 V) >
Programming instructions
Profile S-8.F IO code 8ID code F >
Note: The mounting base for the module is soldseparately.
Data bits (function via AS-Interface) inputoutput D0 IN4O4 D1 -OUT2D2 -OUT3 D3 -OUT4 Parameter bits (programmable via AS-i) function P0 communication monitoringP0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their conditionP1 not used >
I/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Accessories
P2 not usedP3 not used >
VBP-HH1
Ambient conditions
Hand-held programming device
Ambient temperature -25 ... 60 °C (248 ... 333 K) >
VAZ-PK-1,5M-V1-G
Storage temperature -25 ... 85 °C (248 ... 358 K) >
Connection cable module/hand-held pro-
gramming device
Mechanical specifications
VAZ-FK-ED-G2
Protection degree IP67 according to EN 60529Connection cable piercing methodflat cable yellow/flat cable blackinputs/outputs: M12 round
connector specification >
AS-Interface end industrial seal for G2 modules
Mass 100 gMounting Mounting base >
Matching system components
U-G3FF Mounting plate for connection to flat ca-ble (AS-Interface and external auxiliary power)
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com