VAA-2*EA-G2-ZE/E2AS-Interface sensor-/actuator module Technical data Function
General specifications
The VAA-2*EA-G2-ZE/E2 is an AS-Interfacecoupling module with 2inputs and 2outputs.The inputs and outputs are available via a
M12x1 socket. Mechanical contacts and 2-and 3-wire sensors can be connected to theinputs. The outputs are powered via theinternal sensor supply.The module is used to drive motors withdecentralised manufacturer of motor controllers (MOVIS-WITCH from SEW corporation). Each driverequires a 24V input and a 24V output.Connection to the sensors/actuators is pro-
vided via M12x1 screw connections.The IP67 flat module features an integratedaddressing professional jack and is ideal for applicationsin the field. The current switching state ofeach channel is indicated by an LED locatedon the module's top side. The supply of theinputs and outputs is monitored for short cir-cuits. Similarly, an LED is provided to monitorthe AS-Interface communication and to indi-
cate that the module has the address0. If anAS-Interface communication error occurs,the outputs are de-energised.
The U-G3FF mounting base is used as astandard connection to the AS-Interface flatcable. The specially designed base enablesusers to connect flat cables from both sides.This means, for example, that 90° curves canbe laid with very tight radii (variable flat cableguide).
Slave type Standard slave >
Indicators/operating means
LED FAULT error display; LED redred: communication error or address is 0red flashing: overload of sensor supplyLED PWR AS-Interface voltage; LED green >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl professional cabinet LED IN switching state (input); 2 LED yellowLED OUT switching state (output); 2 LED yellow >
Electrical specifications
Protection class III Rated operational voltage U >
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I >
e 30 mA (without sensors) / max. 180 mA >
Input
Number/Type 2 inputs for 2- or 3-wire sensors (PNP), DC Supply from AS-InterfaceVoltage 21 ... 31 V Current loading capacity 150 mA (T >
B 40 °C), 120 mA (T >
B 60 °C), short-circuit proofInput current 8 mA (limited internally) Switching point 0 (unattenuated) 1.5 mA 1 (attenuated) 4.5 mA >
Output
Number/Type 2 electronic outputs, PNPSupply from AS-Interface >
Note: The mounting base for the module is soldseparately.
Current limited by the current loading capacity of the module >
Programming instructions
Profile S-3.FIO code 3 ID code F >
I/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Data bits (function via AS-Interface) inputoutput D0 IN1-D1 IN2- D2 -OUT3D3 -OUT4 Parameter bits (programmable via AS-i) functionP0 communication monitoringP0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition >
Accessories
VBP-HH1 Hand-held programming device
P1 not usedP2 not used >
VAZ-PK-1,5M-V1-G Connection cable module/hand-held pro-gramming device
P3 not used >
Ambient conditions
Ambient temperature -25 ... 60 °C (248 ... 333 K)Storage temperature -25 ... 85 °C (248 ... 358 K) >
VAZ-FK-ED-G2 AS-Interface end professional seal for G2 modules
Mechanical specifications
Protection degree IP67 according to EN 60529 >
Matching system components
Connection cable piercing methodflat cable yellow/flat cable black
inputs/outputs: M12 round connectorMass 100 g >
U-G3FF Mounting plate for connection to flat ca-ble (AS-Interface and external auxiliary power)
Mounting Mounting base >
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com