VBA-4E-G2-ZAAS-Interface sensor module Technical data Function
General specifications
The VBA-4E-G2-ZA is an AS-Interface inter-face module with 4Inputs. Mechanical con-tacts (e.g. push buttons) as well as 2-, 3-
and 4-wire sensors can be connected to theinputs.The IP67 flat module is ideal for applicationsin the field. An addressing professional jack is integratedin the module.The sensors are connected by means ofM12x1 screw connections. An LED is pro-vided for each channel to indicate the currentswitching status. Similarly, an LED is availa-
ble to professional monitor the AS-Interface communica-tion and the indication that the module hasthe address0.The mounting plate U-G3FF is used, asstandard, for connection to the AS-Interface.This lower section enables the flat cable tobe contacted from both sides. If input andoutput modules are used in a mixed system,the flat cable for the internal power dosing
can be inserted in the lower section of thismodule. The module does not access thiscable. The advantage is that both flat cables
can be laid in parallel, without the danger ofthe module being destroyed by an incorrectconnection.An overloading of the internal input supply issignalled to the AS-Interface master via the"Peripheral fault" function. Communicationvia the AS-Interface remains unaffected.
Slave type A/B slave >
Indicators/operating means
LED FAULT error display; LED redred: communication error or address is 0red flashing: overload of sensor supplyLED PWR AS-Interface voltage; LED green >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl industrial cabinet LED IN switching state (input); 4 LED yellow >
Electrical specifications
Protection class IIIRated operational voltage U >
e 26.5 ... 31.6 V from AS-Interface Rated operational current I >
e 40 mA (without sensors) / max. 240 mA >
Input
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DC alternative 2 inputs for 4-wire sensors (PNP), DCSupply from AS-Interface Voltage 21 ... 31 VCurrent loading capacity 200 mA (T >
B 40 °C), 150 mA (T >
B 60 °C), overload-proof and short-circuit proof Input current 8 mA (limited internally)Switching point according to DIN EN 61131-2 (Type 2) 0 (unattenuated) 2 mA1 (attenuated) 4 mA >
Programming instructions
Profile S-0.A.2 IO code 0ID code A >
Note: The mounting base for the module is soldseparately.
ID1 code 7ID2 code 2 Data bits (function via AS-Interface) inputoutput D0 IN1- D1 IN2-D2 IN3- >
I/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories D3 IN4- Parameter bits (programmable via AS-i) function P0 not usedP1 not used P2 not usedP3 not used >
Accessories
Ambient conditions
VBP-HH1
Ambient temperature -25 ... 60 °C (248 ... 333 K) >
Hand-held programming device
Storage temperature -25 ... 85 °C (248 ... 358 K) >
VAZ-PK-1,5M-V1-G
Mechanical specifications
Connection cable module/hand-held pro-gramming device
Protection degree IP67 according to EN 60529Connection cable piercing methodflat cable yellowinputs: M12 round
connector specification >
VAZ-FK-ED-G2
Mass 100 gMounting Mounting base >
Matching system components Notes
U-G3FF
For 4-wire sensors, it is only possible to use plug-in slot IN1 or IN3 for inputs 1+2 or 3+4(jumpered internally).
Mounting plate for connection to flat ca-ble (AS-Interface and external auxiliary power)
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
159