VBA-4E3A-G2-ZA/EA2AS-Interface sensor-/actuator module Technical data Function

General specifications

The VBA-4E3A-G2-ZA/EA2 is an AS-Inter-face module with 4Inputs and 3outputs.Mechanical contacts (e.g. push buttons) as well as 2-, 3- and 4-wire sensors can be con-nected to the inputs. The outputs are elec-tronic outputs, which can be collectivelyloaded with 24VDC and 2A or 1.5A peroutput.The IP67 flat module is ideal for applicationsin the field. An addressing professional jack is integratedin the module.The connection for the sensors/actuators is via M12x1 screw connections. An LED isprovided on the top of the module, for eachchannel, to indicate the current switching sta-tus. Similarly, an LED is provided to monitorthe AS-Interface communication and to indi-cate that the module has the address0.LEDs are also provided to indicate AS-Inter-face voltage and external power supply specifications.The mounting plate U-G2FF is used as standard for the connection to the AS-Inter-face flat cable and the external 24VDC sup-ply. The specially designed base enables the user to connect flat cable from both sides.The device incorporates communicationmonitoring, which switches off power to theoutputs if no communication has taken placeon the AS-Interface line for longer than40ms.An overloading of the internal input supply orof the outputs is signalled to the AS-interfacemaster via the "Peripheral fault" function.Communication via the AS-Interface remainsintact.

Slave type A/B slave
Indicators/operating means
LED FAULT error display; LED redred: communication error or address is 0red flashing: overload of sensor power supply or outputsLED PWR AS-Interface voltage; LED green
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at workI/O ModulesControl professional cabinet LED AUX ext. auxiliary voltage U
AUX ; LED greenLED IN switching state (input); 4 LED yellow LED OUT switching state (output); 3 LED yellow
Electrical specifications
Auxiliary voltage (output) U
AUX 20 ... 30 V DC PELV(protection class 3 according to VDE 0106/IEC 364-4-41)Protection class III Rated operational voltage U
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I
e 40 mA (without sensors) / max. 240 mA
Input
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DC alternative 2 inputs for 4-wire sensors (PNP), DC Supply from AS-InterfaceVoltage 21 ... 31 V Current loading capacity 200 mA (T
B 40 °C), 150 mA (T
B 60 °C), overload-proof and short-circuit proofInput current 8 mA (limited internally) Switching point according to DIN EN 61131-2 (Type 2)0 (unattenuated) 2 mA 1 (attenuated) 4 mA
Output
Number/Type 3 electronic outputs, PNP, overload and short-circuit proofSupply from external auxiliary voltage U
AUX

Note:

Current 4 A total,OUT 1, OUT 2: 2 A per output, OUT 3: 1.5 AVoltage

The mounting base for the module is soldseparately.

(U
I/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories AUX - 0,5 V)
Programming instructions
Profile S-7.A.2 IO code 7ID code A ID1 code 7ID2 code 2 Data bits (function via AS-Interface) inputoutput D0 IN1OUT1 D1 IN2OUT2D2 IN3OUT3

Accessories

VBP-HH1

D3 IN4-

Hand-held programming device

Parameter bits (programmable via AS-i) function P0 not usedP1 not used

VAZ-PK-1,5M-V1-G Connection cable module/hand-held pro- gramming device

P2 not usedP3 not used

VAZ-FK-ED-G2 AS-Interface end professional seal for G2 modules

Ambient conditions
Ambient temperature -25 ... 60 °C (248 ... 333 K) Storage temperature -25 ... 85 °C (248 ... 358 K)
Mechanical specifications

Matching system components

Protection degree IP67 according to EN 60529Connection cable piercing methodflat cable yellow/flat cable blackinputs/outputs: M12 round connector manufacturers

U-G2FF Mounting plate for connection to flat ca-ble (AS-Interface and external auxiliary power)

Mass 150 gMounting Mounting base

Notes

For 4-wire sensors, it is only possible to use plug-in slot IN1 or IN3 for inputs 1+2 or 3+4(jumpered internally).

Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

153

DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
Contents table
page 101 p.101
page 102 p.102
page 103 p.103
page 104 p.104
page 105 p.105
page 106 p.106
page 107 p.107
page 108 p.108
page 109 p.109
page 110 p.110
page 111 p.111
page 112 p.112
page 113 p.113
page 114 p.114
page 115 p.115
page 116 p.116
page 117 p.117
page 118 p.118
page 119 p.119
page 120 p.120
page 121 p.121
page 122 p.122
page 123 p.123
page 124 p.124
page 125 p.125
page 126 p.126
page 127 p.127
page 128 p.128
page 129 p.129
page 130 p.130
page 131 p.131
page 132 p.132
page 133 p.133
page 134 p.134
page 135 p.135
page 136 p.136
page 137 p.137
page 138 p.138
page 139 p.139
page 140 p.140
page 141 p.141
page 142 p.142
page 143 p.143
page 144 p.144
page 145 p.145
page 146 p.146
page 147 p.147
page 148 p.148
page 149 p.149
page 150 p.150
Pages:
1-50
51-100
101-150
151-200
201-250
251-300
301-350
351-356
pdf-page pdf di En 2008-12-49-05