VBA-4E2A-KE1-Z/E2AS-Interface sensor-/actuator module Technical data Function
General specifications
The VBA-4E2A-KE1-Z/E2 AS-interface cou-pling module is a professional cabinet module with4inputs and 2electronic outputs. The hous-
ing, only 22.5mm in width and 48.5mm inheight, takes up little place in the switch cabi-net. The module is mounted by snappingonto the 35mm DIN rail in accordance withEN50022.Plug-in terminals are used for connection. 4-way terminal blocks manufacturers (black) are used for theinputs. The connection of the outputs and theexternal auxiliary supply and AS-Interface is
made through the 2-way terminal blocks (out-puts black, auxiliary voltage gray and AS-Interface yellow). This makes it possible toseparate individual supplier of actuators or to supplypower during commissioning or servicing.The supply of the inputs and the connectedsensors occurs internally via the module(from AS-Interface). An LED on the front con-trol plate is used to display the current
switching state for each input and output.
Slave type A/B slave >
Indicators/operating means
LED FAULT error display; LED redred: communication error or address is 0red flashing: overload of outputsLED PWR AS-Interface voltage; LED green >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at work LED AUX ext. auxiliary voltage U >
AUX ; LED greenLED IN switching state (input); 4 LED yellow LED OUT switching state (output); 2 LED yellow >
Electrical specifications
Auxiliary voltage (output) U >
AUX 20 ... 30 V DC PELVProtection class III Rated operational voltage U >
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I >
e 25 mA (without sensors) / max. 60 mA Overvoltage protection U >
AUX , U >
e : Over voltage category III, safe isolated power sup-plies (PELV) >
Input
Number/Type 4 inputs for 2-wire sensors (PNP), DC or for mechanical con-tactsInput current >
Note: The device is equipped with a watchdog,which switches the outputs to their de-ener-gized state, when on the AS-interface cable
is no communication for more than 40ms.An overload of the outputs is reported by the'periphery error' to the AS-Interface master.Communication over the AS-Interface
remains in effect.
8 mA (limited internally) Switching point according to DIN EN 61131-2 (Type 2)0 (unattenuated) 2 mA 1 (attenuated) 4 mASignal delay < 2 ms (input/AS-Interface) >
I/O ModulesControl cabinetI/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Signal frequency 250 Hz >
Output
Number/Type 2 electronic outputs, PNP, overload and short-circuit proofSupply from external auxiliary voltage U >
AUX Current O1/O2 max. 1.5 A, total 3 A (T >
B 40 °C)O1/O2 max. 1 A, total 2 A (T >
B 70 °C)Voltage (U >
AUX - 0,5 V) Usage category DC-13 >
Programming instructions
Profile S-7.A.0IO code 7 >
Accessories
ID code AID1 code 7 >
VBP-HH1 Hand-held programming device
ID2 code Data bits (function via AS-Interface) inputoutput >
VAZ-PK-1,5M-V1-G
D0 IN1O1D1 IN2O2 >
Connection cable module/hand-held pro-gramming device
D2 IN3-D3 IN4- Parameter bits (programmable via AS-i) functionP0 not used P1 not usedP2 not used P3 not used >
Ambient conditions
Ambient temperature -25 ... 70 °C (248 ... 343 K)Storage temperature -25 ... 85 °C (248 ... 358 K) Relative humidity 90 % , not condensedDegree of soiling 2 >
Mechanical specifications
Protection degree IP20 according to EN 60529 Connection removable terminalsrated connection capacity:rigid/flexible (with and without wire-end ferrules): 0.25mm >
2 ...2.5mm >
2 for multiple-wire connection with two wires of equal cross-sec-tion:
flexible with twin wire-end ferrules: 0.5mm >
2 ...1.5mm >
2 Mass 80 g Mounting DIN rail >
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m
143