VBA-4E3A-KE-ZE/E2AS-Interface sensor-/actuator module Technical data Function

General specifications

The VBA-4E3A-KE-ZE/E2 AS-Interface cou-pling module is a industrial cabinet module with4inputs and 3electronic outputs. The only 22.5mm width housing requires not muchspace in the switch cabinet. The VBA-4E3A-KE-ZE/E2 is installed by snapping on the35mm DIN Rail in accordance withEN50022.The connection type is made through plug-interminals. 4-way terminal blocks suppliers (black) areused for the inputs. The connection of theoutputs and the external auxiliary supply and AS-Interface is made through the 2-way ter-minal blocks (outputs black, Auxiliary voltagegray and AS-Interface yellow). This allowssimple disconnection of single actuators orsupply for commissioning or service.The power supply of the inputs and the con-nected sensors can made as required inter-nal via the module (AS-Interface) or via anexternal voltage source. The switching occurs with the switch in the device. Theselection of the internal input supply is indi-cated via the LED INT. The current switching state of each in- and output is indicated by aLED on the front plate.

Slave type A/B slave
Indicators/operating means
LED FAULT Fault display; Red LEDred: Communication fault or address is 0red, flashing: Overload, internal input supply or outputsLED INT Internal input voltage active; LED green
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at work LED PWR AS-Interface voltage; LED greenLED AUX ext. auxiliary voltage U
AUX ; LED green LED IN switching state (input); 4 LED yellowLED OUT switching state (output); 3 LED yellow
Electrical specifications
Auxiliary voltage (input) U
EXT 12 ... 30 V DC PELV Auxiliary voltage (output) U
AUX 20 ... 30 V DC PELVProtection class III Rated operational voltage U
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I
e 35 mA (without sensors) / max. 190 mA Overvoltage protection U
EXT , U
AUX , U
e : Over voltage category III, industrial safe isolated manufacturers of power supplies (PELV)
Input
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DCSupply from AS-Interface (switch position INT, basic setting) or exter-nal U

Note: The device is equipped with a watchdog,which switches the outputs to their de-ener-gized state, when on the AS-interface cable is no communication for more than 40ms.An overloading of the internal input supply orof the outputs will be reported via the func-tion 'peripheral error' to the AS-Interfacemaster. Communication via the AS-Interfaceremains intact.

EXT (switch position EXT) Voltage 21 ... 31 V DC (INT)Current loading capacity 150 mA, overload- and short-circuit proof (INT)
I/O ModulesControl cabinetI/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Input current 8 mA (limited internally)Switching point according to DIN EN 61131-2 (Type 2) 0 (unattenuated) 2 mA1 (attenuated) 4 mA Signal delay < 2 ms (input/AS-Interface)Signal frequency 250 Hz
Output
Number/Type 3 electronic outputs, PNP, overload and short-circuit proof Supply from external auxiliary voltage U
AUX Current O1 max. 3 A, O2/O3 max. 1.5 A, total 6 A (T
B 40 °C)O1 max. 2 A, O2/O3 max. 1 A, total 4 A (T
B 60 °C) Voltage (U
AUX - 0,5 V)Usage category DC-13
Programming instructions
Profile S-7.A.0

Accessories

IO code 7ID code A

VBP-HH1

ID1 code 7ID2 code 0

Hand-held programming device

Data bits (function via AS-Interface) inputoutput

VAZ-PK-1,5M-V1-G

D0 IN1O1

Connection cable module/hand-held pro-gramming device

D1 IN2O2D2 IN3O3 D3 IN4- Parameter bits (programmable via AS-i) function P0 not usedP1 not used P2 not usedP3 not used
Ambient conditions
Ambient temperature -25 ... 60 °C (248 ... 333 K) Storage temperature -25 ... 85 °C (248 ... 358 K)Relative humidity 90 % , not condensed Degree of soiling 2
Mechanical specifications
Protection degree IP20 according to EN 60529Connection removable terminalsrated connection capacity:rigid/flexible (with and without wire-end ferrules): 0.25mm
2 ...2.5mm
2 for multiple-wire connection with two wires of equal cross-sec-tion:flexible with twin wire-end ferrules: 0.5mm
2 ...1.5mm
2 Mass 150 gMounting DIN rail
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m

129

DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
Contents table
page 101 p.101
page 102 p.102
page 103 p.103
page 104 p.104
page 105 p.105
page 106 p.106
page 107 p.107
page 108 p.108
page 109 p.109
page 110 p.110
page 111 p.111
page 112 p.112
page 113 p.113
page 114 p.114
page 115 p.115
page 116 p.116
page 117 p.117
page 118 p.118
page 119 p.119
page 120 p.120
page 121 p.121
page 122 p.122
page 123 p.123
page 124 p.124
page 125 p.125
page 126 p.126
page 127 p.127
page 128 p.128
page 129 p.129
page 130 p.130
page 131 p.131
page 132 p.132
page 133 p.133
page 134 p.134
page 135 p.135
page 136 p.136
page 137 p.137
page 138 p.138
page 139 p.139
page 140 p.140
page 141 p.141
page 142 p.142
page 143 p.143
page 144 p.144
page 145 p.145
page 146 p.146
page 147 p.147
page 148 p.148
page 149 p.149
page 150 p.150
Pages:
1-50
51-100
101-150
151-200
201-250
251-300
301-350
351-356
pdf-page pdf di En 2008-12-49-05