VAA-4EA-KF2-ZE/RAS-Interface sensor-/actuator module Technical data Function

General specifications

The VAA-4EA-KF2-ZE/R AS-Interface cou-pling module is a industrial cabinet module with4inputs and 4relay outputs. Its design, only 40mm wide, occupies little space in a cabi-net installation. To install the VAA-4EA-KF2-ZE/R, simply snap it onto the 35mm DIN railaccording to EN50022, with the integratedPower Rail.When an AS-Interface master/gateway isused in the cabinet housing, the AS-Interfacesignal is automatically transmitted via thePower Rail. The connection of the module to the AS-Interface cable is accomplished bysimply snapping it onto the DIN rail.The plug-in coded terminals of the inputs andoutputs allow "online" maintenance, i.e.while the system is under power. The termi-nals are coded to prevent incorrect connec-tions.If a master/gateway other than the one in thecabinet housing is used, the connection to the AS-Interface cable is established via thesame terminals. Once the AS-Interface cablehas been connected to the terminals, the AS- Interface signal is automatically transferredto the Power Rail.Power to the module is supplied by the AS-Interface cable and the outputs are poweredexternally (see connection diagram). A pro-gramming professional jack is available for address con-figuration.

Slave type Standard slave
Indicators/operating means
LED PWR/FAULT dual LED green/redgreen: AS-Interface voltagered: communication error or address 0green/red flashing: overload sensor supplyLED IN switching state (input); 4 LED yellow
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at work LED OUT switching state (output); 4 LED yellow
Electrical specifications
Rated operational voltage U
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I
e 80 mA (without sensors) / max. 230 mA
Input
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DC Supply from AS-InterfaceVoltage 21 ... 31 V DC Current loading capacity 150 mA, short-circuit protectedSwitching point 0 (unattenuated) 2 mA1 (attenuated) 4 mA
Output
Number/Type 4 relay outputs Electrical isolation AS-Interface - Outputs: Industrial safe isolation according to EN 50178 (250 V AC)Output - Output: Safe isolation according to EN 50178 (250 V AC)Contact loading 2 A/30 V DC per output2 A/250 V AC per output

Note:

I/O ModulesControl cabinetI/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories

The outputs are de-energised by means ofan integrated watchdog, whenever communi-cation on the AS-Interface cable is inter-rupted for more than 80ms. The watchdogcan be disabled by the parameter bit P0.

Lifetime mechanical: 30 x 10
6 switching cycles electrical: 1 x 10
6 operations (30 V DC, 2 A, ohmic)5 x 10
6 operations (250 V AC, 2 A, cos
6 = 1)4.5 x 10 switching cycles(250 V AC, 2 A, cos = 0.7)
Programming instructions
Profile S-7.FIO code 7 ID code F Data bits (function via AS-Interface) inputoutput D0 IN1OUT1D1 IN2OUT2 D2 IN3OUT3D3 IN4OUT4

Accessories

Parameter bits (programmable via AS-i) functionP0 communication monitoringP0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition

VBP-HH1 Hand-held programming device VAZ-PK-1,5M-V1-G

P1 not usedP2 not used

Connection cable module/hand-held pro-gramming device

P3 not used

UPR-05

Ambient conditions

Universal Power Rail with DIN rail and cover, 5 leads

Ambient temperature -25 ... 70 °C (248 ... 343 K)Storage temperature -25 ... 85 °C (248 ... 358 K)
Mechanical specifications

UPR-E

Protection degree IP20 according to EN 60529

End cap for UPR-03 und UPR-05

Connection removable coded terminals, Power RailMass 170 g Mounting DIN rail
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m

123

DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
Contents table
page 101 p.101
page 102 p.102
page 103 p.103
page 104 p.104
page 105 p.105
page 106 p.106
page 107 p.107
page 108 p.108
page 109 p.109
page 110 p.110
page 111 p.111
page 112 p.112
page 113 p.113
page 114 p.114
page 115 p.115
page 116 p.116
page 117 p.117
page 118 p.118
page 119 p.119
page 120 p.120
page 121 p.121
page 122 p.122
page 123 p.123
page 124 p.124
page 125 p.125
page 126 p.126
page 127 p.127
page 128 p.128
page 129 p.129
page 130 p.130
page 131 p.131
page 132 p.132
page 133 p.133
page 134 p.134
page 135 p.135
page 136 p.136
page 137 p.137
page 138 p.138
page 139 p.139
page 140 p.140
page 141 p.141
page 142 p.142
page 143 p.143
page 144 p.144
page 145 p.145
page 146 p.146
page 147 p.147
page 148 p.148
page 149 p.149
page 150 p.150
Pages:
1-50
51-100
101-150
151-200
201-250
251-300
301-350
351-356
pdf-page pdf di En 2008-12-49-05