VAA-4EA-KF2-ZE/E2AS-Interface sensor-/actuator module Technical data Function
General specifications
The VAA-4EA-KF2-ZE/E2 AS-Interface cou-pling module is a industrial cabinet module with4inputs and 4electronic outputs. The VAA-
4EA-KF2-ZE/E2 is installed by snapping itonto the 35mm DIN Rail per EN50022, withthe integrated Power Rail.When an AS-Interface master/gateway isused in the cabinet housing, the AS-Interfacesignal is automatically transmitted via thePower Rail. The connection of the module tothe AS-Interface cable is accomplished bysimply snapping it onto the DIN Rail.
The plug-in coded terminals of the inputs andoutputs allow "online" maintenance, i.e.while the system is under power. The termi-nals are coded to prevent incorrect connec-tions.If a master/gateway other than the one in thecabinet housing is used, the connection tothe AS-Interface cable is established via thesame terminals. Once the AS-Interface cable
has been connected to the terminals, the AS-Interface signal is automatically transferredto the Power Rail.
Power to the module and to the inputs is sup-plied by the AS-Interface cable and the out-puts are powered externally (see connectiondiagram). A programming professional jack is available foraddress configuration.
Slave type Standard slave >
Indicators/operating means
LED PWR/FAULT dual LED green/redgreen: AS-Interface voltagered: communication error or address 0green/red flashing: overload sensor supplyLED AUX ext. auxiliary voltage U >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at work AUX ; LED green LED IN switching state (input); 4 LED yellowLED OUT switching state (output); 4 LED yellow >
Electrical specifications
Auxiliary voltage (output) U >
AUX 20 ... 30 V DC PELV Protection class IIIRated operational voltage U >
e 26.5 ... 31.6 V from AS-Interface Rated operational current I >
e 50 mA (without sensors) / max. 200 mA >
Input
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DCSupply from AS-Interface Voltage 21 ... 31 V DCCurrent loading capacity 150 mA, short-circuit protected Switching point 0 (unattenuated) 2 mA 1 (attenuated) 4 mA >
Note:
Output
The outputs are de-energised by means ofan integrated watchdog, whenever communi-cation on the AS-Interface cable is inter-rupted for more than 80ms. The watchdogcan be disabled by the parameter bit P0.If a short circuit occurs in the sensor supply,the AS-Interface master will indicate an errorand the module will disconnect from the AS-Interface.
Number/Type 4 electronic outputs, PNPSupply from external auxiliary voltage U >
I/O ModulesControl cabinetI/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories AUX Current 2 A per output , 8 A per moduleVoltage (U >
AUX - 0,5 V) >
Programming instructions
Profile S-7.F IO code 7ID code F Data bits (function via AS-Interface) inputoutput D0 IN1OUT1 D1 IN2OUT2D2 IN3OUT3 D3 IN4OUT4 Parameter bits (programmable via AS-i) function P0 communication monitoringP0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their conditionP1 not used >
Accessories
P2 not usedP3 not used >
VBP-HH1 Hand-held programming device
Ambient conditions
Ambient temperature -25 ... 70 °C (248 ... 343 K) >
VAZ-PK-1,5M-V1-G
Storage temperature -25 ... 85 °C (248 ... 358 K) >
Connection cable module/hand-held pro-gramming device
Mechanical specifications
Protection degree IP20 according to EN 60529Connection removable coded terminals, Power Rail >
UPR-05
Mass 170 gMounting DIN rail >
Universal Power Rail with DIN rail and cover, 5 leads UPR-E End cap for UPR-03 und UPR-05
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m
121