VAA-4EA-KF-DKAS-Interface data coupler Technical data Function
General specifications
The data coupler interface module VAA-4EA-KF-DK is used when the output bits of anAS-Interface circuit are to be used as the
input bits of another AS-Interface circuit. Thedata coupler is equipped with two AS-Inter-face connections for this purpose, each rep-resenting a 4EA module. The output bits ofthe AS-Interface circuit1 are represented onthe AS-Interface circuit2 as input bits andvice versa. This enables data exchange to becarried out in both directions without havingto transfer the data via the higher-level con-
trol system. This is a particular advantage intime-critical applications. The addressingprocedures for the two integrated AS-Inter-face slaves are carried out independently ofeach other. Two addressing jacks are pro-vided for this purpose.Because two independent AS-Interface mod-ules are used, the related inputs and outputsare galvanically isolated from each other.
This avoids problems with potential shifts(earth potential). The status of all the outputsis indicated via 8LEDs located on the mod-
ule's front panel. Two additional LEDs indi-cate the AS-Interface voltage on the twocircuits.Its design, only 20mm wide, occupies littlespace in a professional cabinet installation. The VAA-4EA-KF-DK is installed by snapping it ontothe 35mm DIN rail per EN50022, with theinserted Power Rail. This ensures that AS-Interface circuit1 of the module is automati-cally connected to the AS-Interface transmis-sion line, if other cabinet modules or amaster/gateway are operating on this circuit.If this is not the case, the AS-Interface trans-mission line is connected to the pluggable,coded terminals. This is absolutely essentialfor AS-Interface circuit2.
Slave type Standard slave >
Indicators/operating means
LED PWR AS-Interface voltage; 2 LED greenLED OUT switching state (output); 8 LED yellowO10-O13: AS-Interface 1;O20-O23: AS-Interface 2 >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at work Electrical specifications
Protection class III Rated operational voltage U >
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I >
e 30 mA >
Input
Number/Type 4 internal inputs per AS-Interface circuit 1+2 >
Output
Number/Type 4 internal outputs per AS-Interface circuit 1+2 >
Programming instructions
Profile S-7.F IO code 7ID code F Data bits (function via AS-Interface) inputoutput D0 IN1OUT1 D1 IN2OUT2D2 IN3OUT3 D3 IN4OUT4 >
I/O ModulesControl cabinetI/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Parameter bits (programmable via AS-i) P0 not usedP1 not used P2 not usedP3 not used >
Ambient conditions
Ambient temperature -25 ... 70 °C (248 ... 343 K) Storage temperature -25 ... 85 °C (248 ... 358 K) >
Mechanical specifications
Protection degree IP20 according to EN 60529Connection removable coded terminals, Power Rail Mass 130 gMounting DIN rail >
Accessories
VBP-HH1 Hand-held programming device VAZ-PK-1,5M-V1-G Connection cable module/hand-held pro-gramming device UPR-05 Universal Power Rail with DIN rail and cover, 5 leads UPR-E End cap for UPR-03 und UPR-05
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m
119