VAA-4A-KF-E2AS-Interface supplier of actuator module Technical data Function
Indicators/operating means
The VAA-4A-KF-E2 AS-Interface couplingmodule is a professional cabinet module with 4electronicoutputs. Its design, only 20mm wide, occu-
pies only little space in a cabinet installation.The VAA-4E-KF-E2 is installed by snapping itonto a 35mm DIN rail according toEN50022, with the integrated Power Rail.When an AS-Interface master/gateway isused in the cabinet housing, the AS-Interfacesignal is automatically transmitted via thePower Rail. The connection of the module tothe AS-Interface cable is accomplished by
simply snapping it onto the DIN rail.The plug-in coded terminals of the inputs andoutputs allow "online" maintenance, i.e.while the system is under power. The termi-nals are coded to prevent incorrect connec-tions.If a master/gateway other than the one in thecabinet housing is used, the connection tothe AS-Interface cable is established via the
same terminals. Once the AS-Interface cablehas been connected to the terminals, the AS-Interface signal is automatically transferred
to the Power Rail.Power to the module is supplied by the AS-Interface cable and the outputs are poweredexternally (see connection diagram). A pro-gramming professional jack is available for address con-figuration.
LED PWR/FAULT dual-LED green/redgreen: AS-Interface voltage, normal operationred: communication error or address 0LED OUT switching state (output); 4 LED yellow >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at work LED AE ext. auxiliary voltage U >
AUX ; LED green >
Electrical specifications
Auxiliary voltage (output) U >
AUX 20 ... 30 V DC PELVProtection class III Rated operational voltage U >
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I >
e 30 mA >
Output
Number/Type 4 electronic outputs, PNP Supply from external auxiliary voltage U >
AUX Current 2 A per output , 8 A per module Voltage (U >
AUX - 0,5 V) >
Programming instructions
Profile S-8.FIO code 8 ID code F Data bits (function via AS-Interface) inputoutput D0 IN4O4D1 -OUT2 >
Note:
D2 -OUT3D3 -OUT4 >
The outputs are de-energised via an inte-grated watchdog, whenever communicationon the AS-Interface cable is interrupted formore than 80ms. The watchdog can be disa-bled by the P0 parameter bit.
I/O ModulesControl cabinetI/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories Parameter bits (programmable via AS-i) functionP0 communication monitoringP0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition P1 not usedP2 not used P3 not used >
Ambient conditions
Ambient temperature -25 ... 70 °C (248 ... 343 K)Storage temperature -25 ... 85 °C (248 ... 358 K) >
Mechanical specifications
Protection degree IP20 according to EN 60529 >
Accessories
Connection removable coded terminals, Power RailMass 130 g >
VBP-HH1
Mounting DIN rail >
Hand-held programming device VAZ-PK-1,5M-V1-G Connection cable module/hand-held pro-
gramming device UPR-05 Universal Power Rail with DIN rail and cover, 5 leads UPR-E End cap for UPR-03 und UPR-05
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m