VAA-4EA-KF-ZE/RAS-Interface sensor-/actuator module Technical data Function
General specifications
The VAA-4EA-KF-ZE/R AS-Interface cou-pling module is a industrial cabinet module with4inputs and 4relay outputs. Its design, only
40mm wide, occupies little space in a cabi-net installation. The VAA-4EA-KF-ZE/R isinstalled by snapping it onto the 35mm DINRail per EN50022, with the integrated PowerRail.When an AS-Interface master/gateway isused in the cabinet housing, the AS-Interfacesignal is automatically transmitted via thePower Rail. The connection of the module to
the AS-Interface cable is accomplished bysimply snapping it onto the DIN Rail.The plug-in coded terminals of the inputs andoutputs allow "online" maintenance, i.e.while the system is under power. The termi-nals are coded to prevent incorrect connec-tions.If a master/gateway other than the one in thecabinet housing is used, the connection to
the AS-Interface cable is established via thesame terminals. Once the AS-Interface cablehas been connected to the terminals, the AS-
Interface signal is automatically transferredto the Power Rail.Power to the module is supplied by the AS-Interface cable and the inputs and outputsare powered externally (see connection dia-gram). A programming professional jack is available foraddress configuration.
Slave type Standard slave >
Indicators/operating means
LED PWR/FAULT dual-LED green/redgreen: AS-Interface voltage, normal operationred: communication error or address 0LED IN switching state (input); 4 LED yellow >
Masters and GatewaysPower Supplies, Extender, RepeatersSafety at work LED OUT switching state (output); 4 LED yellow >
Electrical specifications
Rated operational voltage U >
e 26.5 ... 31.6 V from AS-InterfaceRated operational current I >
e 110 mA >
Input
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DC Supply externalSwitching point 0 (unattenuated) 2 mA1 (attenuated) 4 mA >
Output
Number/Type 4 relay outputs Electrical isolation AS-Interface - Outputs:
Industrial safe isolation according to EN 50178 (250 V AC)Output - Output: Safe isolation according to EN 50178 (250 V AC)Contact loading 2 A/30 V DC per output2 A/250 V AC per output >
Note:
Lifetime mechanical: 30 x 10 >
6 switching cycles electrical:1 x 10 >
The outputs are de-energised by means ofan integrated watchdog, whenever communi-cation on the AS-Interface cable is inter-rupted for more than 80ms. The watchdogcan be disabled by the parameter bit P0.
I/O ModulesControl cabinetI/O ModulesField applicationAnalogue modulesOther modulesInductive sensorsPhotoelectric sensorsRotary encodersAccessories 6 6 operations (30 V DC, 2 A, ohmic)5 x 10 operations (250 V AC, 2 A, cos = 1)4.5 x 10 >
6 switching cycles(250 V AC, 2 A, cos = 0.7) >
Programming instructions
Profile S-7.FIO code 7 ID code F Data bits (function via AS-Interface) inputoutput D0 IN1OUT1D1 IN2OUT2 D2 IN3OUT3D3 IN4OUT4 Parameter bits (programmable via AS-i) functionP0 communication monitoringP0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition >
Accessories
VBP-HH1 Hand-held programming device
P1 not usedP2 not used >
UPR-05 Universal Power Rail with DIN rail and cover, 5 leads
P3 not used >
Ambient conditions
Ambient temperature -25 ... 70 °C (248 ... 343 K)Storage temperature -25 ... 85 °C (248 ... 358 K) >
VAZ-PK-1,5M-V1-G Connection cable module/hand-held pro-gramming device
Mechanical specifications
Protection degree IP20 according to EN 60529 Connection removable coded terminals, Power RailMass 170 g >
UPR-E End cap for UPR-03 und UPR-05
Mounting DIN rail >
Issue date 2004-11-19 - Catalogue AS-Interface 2004/2005 Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in German y Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.co m
113