Discharge Capacity Chart for Inverted Bucket Traps
ACTUAL CONTINUOUS DISCHARGE CAPACITY OF TRAPS IN KILOGRAMS OF HOT CONDENSATE PER HOUR
DIFFERENTIAL PRESSURE (bar)
Model
Ul 1 1 IL»C
Size
0.25
0.5
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.5
19.0
21.0
23.0
25.0
DISCHARGE
CAPACITY
2.5
80
100
120
150
180
200
220
230
250
260
270
280
290
300
310
315
330
340
350
370
390
410
430
2.8
90
120
170
230
260
310
350
390
420
460
480
520
560
580
620
650
680
710
730
PT25-15
3.2
120
150
200
280
340
380
430
480
540
580
620
660
700
740
780
PT25-20L
4.0
150
220
290
380
450
520
580
650
720
780
4.8
320
380
460
600
680
750
800
6.4
360
470
600
720
4.0
150
220
290
380
450
520
580
650
720
780
850
940
1000
1080
1150
1250
1350
1430
1500
1550
1600
1680
1800
4.8
320
350
400
520
620
720
800
880
950
1025
1075
1175
1250
1300
1400
1500
1600
1700
1850
5.6
340
400
480
650
780
900
1025
1100
1175
1275
1375
1500
1600
1725
1850
1950
PT25-20
6.4
380
450
600
850
1075
1200
1300
1425
1575
1700
1875
2000
2100
PT25-25L
7.9
500
620
760
1000
1175
1325
1475
1650
1800
1900
8.7
640
740
900
1150
1325
1500
1700
1900
9.5
950
1150
1300
1600
1900
12.5
1200
1450
1700
4.8
320
350
400
520
620
720
800
880
950
1025
1075
1175
1250
1300
1400
1500
1600
1700
1850
2000
2200
2350
2500
6.4
380
420
650
1000
1200
1400
1600
1800
2000
2150
2300
2500
2650
2800
2950
3100
3300
3450
3700
7.0
500
640
1000
1400
1750
2000
2250
2500
2650
2800
2900
3050
3250
3400
3600
3800
4000
PT25-25
7.9
700
900
1150
1700
2100
2500
2750
3000
3300
3600
3800
4000
4200
4400
8.7
850
1100
1500
2000
2500
2900
3200
3500
3700
3900
4100
9.5
1000
1200
1600
2250
2800
3300
3650
3850
4100
11.2
1200
1500
1900
2500
3250
3800
-----
14.3
1500
2100
2850
4100
19.0
2300
3400
4000
9.5
1000
1200
1600
2250
2800
3300
3650
3850
4100
4400
4700
5100
5500
6000
6400
6800
7200
7600
8000
8500
9000
9800
10800
11.0
1200
1500
2050
2750
3450
4000
4700
5200
5800
6200
6800
7300
7800
8000
8500
9000
9300
9700
10000
PT25-40
13.0
1600
2100
3000
4150
5000
5800
6600
7200
7900
8700
9300
9800
10200
10500
PT25-50
15.0
2600
3400
4600
6300
7700
8600
9200
9900
20.5
3600
4600
6400
8100
9100
27.5
5000
6300
7800
9000
32.0
6400
8500
10000
Guidelines on use of Capacity Chart
• Go to the differential pressure column corresponding to or slightly higher than, but not less than the operating differential pressure at which the trap is to be used. Move vertically downwards and select a suitable model and orifice size.
• The selected capacity should be equal to or higher than the condensate load after including a safety factor of 2 to 3. Oversizing is not recommended.
• Example - Operating conditions = I) Inlet press. 4 bar(g) II) Back press. 1 bar(g) III) Condensate load 480 kg/hr. IV) Safety factor 2. Model Selected: PT25-20 • Orifice size : 6.4mm • Capacity 1075 kg/hr @ a diff. press. of 3 bar.
|