PENN0NT
PT22
Inverted Bucket Steam Traps - (Cast Iron)
MATERIAL:
No
PART
MATERIAL
QTY.
(Nos.)
1.
BODY
CAST IRON
01
2.
COVER
CAST IRON
01
3.
BUCKET ASSLY.
AISI 304
01
4.
LEVER ASSLY.
AISI 304
01
5.
VALVE SEAT (HARDENED)
13% CR STEEL / AISI 410/420
01
6.
BRACKET
AISI 304
01
7.
VALVE PIN (HARDENED)
13% CR STEEL / AISI 410/420
01
8.
GASKET (COVER)
CAF / Non CAF
01
9.
BOLT
ASTMA193 Gr. B7
06
10.
PLUG
CARBON STEEL
02
11.
GASKET (PLUG)
CAF / Non CAF
02
12.
LOCATING TUBE
STAINLESS STEEL
01
DIMENSIONS - Nominal in mm
MODEL
SIZE
A
B
C
D
Wt.
PT22-15 PT22-20
DN15, 20
120
100
130
71
2.7 kg
TRAP DISCHARGE CAPACITY IN kg/hr
Model
Orifice Size
DIFFERENTIAL PRESSURE (bar)
0.5
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.5
10
10.5
PT22-15 PT22-20
2.5 mm
40
80
125
140
180
190
210
225
245
260
265
2.8 mm
65
115
180
215
250
265
280
290
300
-----
-----
3.2 mm
110
160
210
250
280
-----
-----
-----
-----
-----
-----
Guidelines on use of Capacity Chart
• Go to the differential pressure column corresponding to or slightly higher than, but not less than the operating differential pressure at which the trap is to be used. Move vertically downwards and select a suitable model and orifice size.
• The selected capacity should be equal to or higher than the condensate load after including a safety factor of 2 to 3. Oversizing is not recommended.
• Example - Operating conditions = l) Inlet press. 4bar(g) ll) Back press. 1 bar(g) lll) Condensate load 68 kg/hr. lV) Safety factor 2. Model Selected: PT22-15 • Orifice Size : 2.5 mm • Capacity 140 kg/hr @ a diff. press. of 3 bar
HOWTOORDER: PT22-20 DN20 BSP AP
ORDERING INFORMATION:
1) Inlet Pressure in bar (g)
2) Back Pressure in bar (g)
3) Operating Temperature in °C
4) Condensate Load in kg/hr
5) Size & Model
6) End Connections
AVAILABLE SPARES:
SPARE KIT: Valve Pin, Valve Seat, Bracket & Lever Assly. (Op. diff. press. should be specified) Bucket Assly, Set of Gaskets.
Local regulations may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only. In the interest of development and improvement of the product, we reserve the right to change the specifications without prior notice.
M_ USA - 10 Parsonage Road, Suite 312, Edison, NJ, Tel.: 877-597-TRAP(8727) Fax:1-866-682-1244. ICFmmmwtFmE Email: info@pennantcorp.com Website: www.pennantcorp.com
INDIA - S.No. 116 (New), Gat No. 976 (Old), Wadki, Taluka Haveli, Pune - 412 308, INDIA.
Tel.: +91 (0) 20 2698 9709, Telefax: +91 (0) 20 2698 9470 §
Email: enq@pennantindia.com Website www.pennantindia.com May
|