2 Sound Patterns
40
85dB at 1m
* Communication protocol : RS-232C
* Baud rate : 9600bps
* Data length : 8 bits
* Stop bit : 1 bit
* Parity : None
* Flow control : None
* Communication mode : Asynchronous
* Transmission mode : Half duplex
* Transmission code : ASCII
* Return code : ACK [06H]
NACK [15H]
Communication Data / Settings
Control of PHE-3FBE1 / PHC-100A
Output No.
1
2
3
4
5
6
7
8
Function1
Steady Red On
Steady Amber On
Steady Green On
Alarm 1 On
Alarm 2 On
Flashing Red On
Flashing Amber On
Flashing Green On
The above example shows how to turn on the following Output Nos : 6, 3, 2, 1
PHE-3FBE1
RS-232C Controlled Signal Tower
Signal Tower can be controlled
directly by PC through RS-232C.
Dimensions
Specifications
(mm)
Communication Interface
Communication Method
Communication Speed
Data Bit
Stop Bit
Parity Bit
Flow Control
I/O Port
Flashing Rate
Sound Level
Sound Alarm
Dimensions
Supply Power Source
Power Consumption
Operating Temperature Range
Humidity
PHE-3FBE1
RS-232C (Based on EIA)
Half Duplex, Start-Stop, Asynchronous
9,600bps
8bit
1bit
None
None
D-Sub9P Male Connector
60 times per minute
Adjustable from 70 to 85dB (at 1m)
2 alarms (Slow intermittent tone, fast intermittent tone)
100259115mm
AC Adaptor (Sold separately)
7.1v
0~40
20~80%RH (w/o dew condensation)
Model
Communication
Settings
Signal Tower
Section
Base Section
RS-232C straight through cable is not included.
-
RS-232C
DC 24V
+
35 12
228
259
115 (2.5)
40
100
31
(35)
This product requires the knowledge to program the ASCII command to output through RS-232C port.
Alarm is adjustable up to 85dB at 1m
High-volume alarms (two patterns) can be heard even in a
noisy factory.
Bright LED signal tower
PATLITEs original double reflection system with its
exclusive hybrid prism-cut lens and 3 color LED modules
create distinctive illumination that is bright and even.
Light and alarm functions can be turned off by pressing
the reset switch on the base.
25 PHE-3FBE1
Header
ID No.
Output Action
Output Select
End code
@ [40H]
! [21H]
1Byte
2Byte
1Byte
2Bytes
1Byte
? ? [3FH] [3FH]
Please use the default value [??], which
allows this product to function without
specifying an ID No.
0 [30H] Output Off
1 [31H] Output On
? [3FH] Enter ID No
Example
ASCII [Hex]
Bits (BCD)
Output No.
Data1
2 [32H]
00110010
8765
Data2
7 [37H]
00110111
4321
@? ? 1 2 7 !
The position of the '1' in the Binary Coded
Decimal value specifies the Output No. acted
upon according to the Output Action Byte