You may also be interested in
CCTV camera, Gas sensor, Oxygen analyzer, Camera, Transmitter
Text version of the page
Control Systems Transmitters Sensors Accessories
WWW.OLIVER-IGD.CO.UK OLIVER IGD
APPLICATION DATA SHEET
OLIVER IGD
CO
H2SCO2
NOSO2NO2
CH4
Pepper Road Tel: +44 (0)161 483 1415
International Gas Detectors Bramhall Technology Park Fax: +44 (0) 161 484 2345
Stockport Email: sales@oliver-igd.co.uk
SK7 5BW Website: www.oliver-igd.co.uk
England
TOCSIN 903
E E X d L o c a l G a s D e t e c t o r
C o n t r o l a n d D i s p l a y U n i t
G e n e r a l S p e c i f i c a t i o n
4-20mA Output
Alarm Relay Output Option
Digital Addressable I/O Option
Exd Certified
ATEX Certified
Digital Display, Concentration, Alarms and
Fault Status
Easy Calibration One Man Calibration
Now Available with HARToption
See Tocsin 102 series Gas Detector data sheet for sensor specification and type
The Tocsin 903 provides a local display and control facility for the Tocsin 102 series or pellistor gas detectors
in Zone 1 and 2 hazardous areas .In addition to being equipped as a 4 -20mA process transmitter the Tocsin
903 can also be fitted with serial addressable capability either using the Oliver IGD data highway to integrate
to 700 or 900 series controllers or optionally as a HART device. The unit is fully compatible with Tocsin 700
and Tocsin 900 Control Panels which offer both addressable and analogue inputs as well as Modbus serial
outputs. More conventionally the Tocsin 903 can be interfaced directly into DCS/BMS systems using its 4-
20mA Process output. An alarm relay output card is available.
II 2 D G
x d IIC T6
0518
Epsilon07ATEX2287x
Ingress Protection IP66
18 to 32V DC With Relay Option Typically 4 W
12 to 32V DC Without Relay Option (Catalytic Only)
Ref ROS44D
E
Electrical Outputs 3 Wire 4-20mA (4 Wire Addressable Capability)
Temperature -10°c to +55°c
Humidity 15 to 90% RH non-condensing
Ingress Protection IP66
JB Housing Material Junction Box, Copper Free Aluminium Alloy Epoxy Coated
Option for 316 Stainless Stee l and Marine Paint Finishes
Sensor Housing Material Sensor ,Stainless Steel 316 S16
Explosion Protection Junction Box, EExd IIC T6 I I 2 D G
Explosion Protection Sensor EEx d IIC T6 II 2 D G
Housing Dimensions (mm) 110 Diameter x 127 High Plus detector option
Cable Entry 2 x M20, NPT Options
1 x M20 Detector Entry
Power supply
Weight (Std Al Housing) 1.5Kg
HART COMMUNICAT ION FOUNDAT ION
NEW WITH OPTIONAL
023827
|
|