To Protect Electrical Workers from Arc Flash Exposures
Tech Sheet
Description Related Products Ordering Application Headlines
Oberon offers two blankets: 15 KA and 25 KA.
• The 15 KA blanket is constructed of non-combustible material.
It will not ignite and burn even if flame is applied directly to the fabric.
Oberon is the only company that offers a blanket from
non-combustible fabric.
• The 25 KA blanket is primarily made of FR Kevlar®. Kevlar will burn as
only long as there is a source of ignition, i.e., flame from arc or burning
pieces of insulation. The fabric will self extingush once there is
no longer a source of ignition.
Blankets are hung between a potential arc source and the worker or equipment to be protected. To prevent the force
of the arc going downward (toward the floor and redirected up to the individual), the lower portion of the blanket
can be formed in a J under the arc source and toward the wall so the arc will be deflected upward. Never wrap a
blanket around a splice.
The explosive force of the air expanding (the volume of air increases as it heats up) and metal vaporizing cannot be
contained by the strength of even Kevlar. The force must have someplace to go. The blanket’s purpose is to redirect
the force.
#ARC-BLNKT-15KA-S (15KA Blanket, Size 4’x5’)
#ARC-BLNKT-15KA-L (15KA Blanket, Size 5’x8’)
#ARC-BLNKT-25KA-S (25KA Blanket, Size 4’x5’)
#ARC-BLNKT-25KA-L (25KA Blanket, Size 5’x8’)
NOTE: Custom sizes are available. Contact Oberon Customer Service for details
Since there is no industry standard for testing blankets, Oberon developed the following method:
A 750 KCMIL cable with a 3mm splice, supported horizontally 2' off the floor on brackets, was placed 6" away from a
solid vertical wall. The blanket was mounted parallel to and 12" from the back wall, with the splice 6" from the back
surface of the blanket. The blanket is held in place by straps with adjustable brackets.
To create the fault, a sheetrock screw was screwed into the splice and a ground wire connected to the protruding
screw. The cable was energized with 13 KV with a fault current of 7000A clearing time of 8 cycles.
The purpose of the test is to ensure that the multiple-layered arc suppression blanket redirects the energy (thermal
and blast) to the sides and up – not out toward the individual. The blanket must not allow the thermal energy to burn
through all layers. It must also not have particles of the splice and molten metal penetrate the blanket. Most of the
damage to the blanket is in the general area of the splice, a circle 6"-12" in diameter.
22 Logan St. - New Bedford, MA 02740-EEUU
Tel.: 1. 508.999.4442
1.800.322.3348 Presione 9 para Español
Fax: 508.999.4443
Tel.: (55)5350-1460 para llamarnos desde México
sales@oberoncompany.com
www.oberoncompany.com
- HVS-4B-HM FreshAir Hood-mounted Hood Ventilation System
- CV-ARC Jacket-style Arc Flash Cooling Vest
- CVE-ARC Pull over-style Arc Flash Cooling Vest
- TOOLKIT-9ROLL 9-Piece Insulated Tool Kit
- TOOLKIT-DELUXE 30-Piece Insulated Tool Kit
|
|