| | ELECTRICAL DATA | VOLTAGE CURRENT | |
| | Node Power | 24 VDC +/- 10% 0.040 amps. | |
| | Bus Power | 11-25 VDC 0.025 amps. | |
| | Valve & Discrete I/O | 24 VDC +/- 10% 8 amps, maximum | |
| | | Single key 4 pin MINI type (male) | |
| | Communication Connector | Single key 5 pin MINI or 12mm micro type (male) | |
| | LED's | Module Status, Network status, Industrial fuse Integrity and Auxiliary power status | |
| | OPERATING DATA | |
| | Temperature Range | -10° to +115° F (-23° to +46° C) | |
| | Humidity | 95% relative humidity, non condensing | |
| | Moisture | Designed to meet NEMA 4 / IP65 requirements | |
| | CONFIGURATION DATA | |
| | Communication Module | Contains all communication electronics as well as short circuit protected driver circuitry for up to 32 valve solenoids | |
| | Manual Configuration Module (MCM) | Optional module containing DIP and rotary switches for setting device configuration data. Note: Use option G08 In "NX" model number | |
| | Maximum Valve Solenoid Outputs | 32 | |
| | Maximum Discrete I/O Points | Various Combinations of 160 outputs and 80 Inputs | |
| | NETWORK DATA | |
| | Supported Baud Rates | 125K, 250K, 500K and Autobaud | |
| | Supported Connection Types | Polled, Cyclic, Change of State (COS) and Combination Message Capability | |
| | Bus Connector | Single key 5 pin MINI or 12mm micro type (male) | |
| | Diagnostics | Shorts and open load conditions from valve solenoid colls & outputs are monitored | |
| | Special Features | Supports Auto-Device Replacement (ADR) | |
| | | | |